Plan Review Notes
Plan Review Notes For Permit 02100085
Permit Number 02100085
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-07 00:00:00THIS PERMIT IS SUBJECT TO THE FOLLOWING
 PROVISIONS:
  
 1SHEET T-2 DECLARES THE NYC BUILDING
 CODE.PROVIDE A SIGNED AND SEALED
 STATEMENT THAT THE DESIGN IS IN
 ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, 2001 EDITION.
  
  
 2SHEET T-2 DECLARES DESIGN TO ACI
 318-89.PLEASE REVISE AND INSURE
 COMPLIANCE WITH ACI-99.
  
 3SHEET A-3, NOTE #3,SPECIFY THE AMOUNT
 OF TENSION THAT WILL BE APPLIED TO THE
 CABLES.
  
 4PROVIDE A SIGNED AND SEALED COPY OF
 THE "TECHNICAL SPECIFICATION MANUAL"
 CALLED OUT ON SHEET T-1 AS BEING "PART
 OF THIS PROJECT"
  
 5SPECIFY WHICH EIFS SYSTEM IS TO BE
 USED AND THE REFERENCE NUMBER FOR
 PRODUCT ACCEPTANCE FROM A RECOGNIZED
 TESTING LABORATORY OR CODE AGENCY.
  
 6WHAT IS MEANT BY THE TERM
 "DEDEFINED"AS IN LOOSE CABLES SHALL BE
 DEDEFINED?
  
 7 SECTIONS 5/A9 & 9/A9.PROVIDE
 SPECIFIC FASTENER AND CONNECTION
 METHODS FOR THE BENT PLATE CONNECTION
 TO THE MASONRY AND TO THE METAL STUDS.
  
 8IF THE BENT PLATES ARE TO FASTEN
 EVERY OTHER STUD TO THE BUILDING, HOW
 ARE THE INTERMEDIATE STUDS SUPPORTED?
  
 9SPECIFY THE 1/2 INCH EXTERIOR SHEATH
 ING TO BE USED AND THE FASTENING METHOD.
  
 10THE PLANS REFENCE "GROUT" IN SEVERAL
 PLACES.SPECIFY THE INTENDED DESIGN
 STRENGTH.
  
 11SECTION 1/A-10, SPECIFY THE WELDS
 AND GROUT STRENGTH TO BE USED.