Plan Review Notes
Plan Review Notes For Permit 02100056
Permit Number 02100056
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-07 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUN TY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THE ENERGY CODE FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER OR HIS AGENT. SEE
 FBC 13-600.3ABC2
  
 MIAMI-DADE NOA #01-1031.06 HAS ILLEGIBLE
 DRAWINGS AND THE COMPONENTS ARE NOT
 SELECTED.
  
 THE NORANDEX PRODUCT CERTIFICATION HAS
 ILLEGIBLE PAGES AND THE COMPONENTS,
 (INCLUDING ANCHOR METHODS), ARE NOT
 SELECTED
  
 NOA #00-1106.03 DOES NOT HAVE THE
 COMPONENTS AND INSTALLATION METHOD
 SELECTED.
  
 THE WAYNE DALTON DOORS ARE NOT A
 RECOGNIZED TESTING AGENCY.
  
 THE SBCCI REPORT #2036 FOR THE SHUTTERS
 DOES NOT HAVE THE COMPONENTS AND
 FASTENERS SELECTED.NOTE, READ THE
 LIMITATIONS AND COMPARE THE MATERIALS
 TO THOSE SPECIFIED ON THE PLANS.