Plan Review Notes
Plan Review Notes For Permit 02100056
Permit Number 02100056
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE LAUNDRY CIRCUIT @
 1500 VA PER 220-16.REVISE CALCS.
  
 3} PLEASE INCLUDE ALL A/C UNITS IN LOAD
 CALCS.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE CHECK ELECTRICAL NOTE #18
 REGARDING 210-12,FOR ACCURACY.
  
 6} PLEASE NOTE THAT A SMOKE DETECTOR IS
 REQUIRED OUTSIDE THE MASTER SUITE PER
 8-1.4.1.6.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392