| Plan Review Notes For Permit 02100056 |
| Permit Number |
02100056 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | ON THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE LAUNDRY CIRCUIT @ | | | 1500 VA PER 220-16.REVISE CALCS. | | | | | | 3} PLEASE INCLUDE ALL A/C UNITS IN LOAD | | | CALCS. | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} PLEASE CHECK ELECTRICAL NOTE #18 | | | REGARDING 210-12,FOR ACCURACY. | | | | | | 6} PLEASE NOTE THAT A SMOKE DETECTOR IS | | | REQUIRED OUTSIDE THE MASTER SUITE PER | | | 8-1.4.1.6.2 NFPA-72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|