| Notes |
| Date |
Text |
| 2003-03-04 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} THE ELECTRICAL SUB-PANEL SHOWS 1 60 | | | AMP CIRCUIT FOR IT'S LOAD.PLEASE SHOW | | | CORRECT LOADS. | | | | | | 2} THERE IS NO EQUIPMENT GROUND FROM | | | PANEL "A" TO SUB-PANEL. | | | | | | 3} RECEPTACLE SPACING IN THE LIVING ROOM | | | & BED ROOM #3,DO NOT COMPLY WITH 210-52 | | | | | | PLEASE MAKE NECESSARY CORRECTIONS AND | | | RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|