| Date |
Text |
| 2002-12-23 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE A SOIL TEST REPORT PER CITY |
| | OF WPB AMENDMENTS TO THE FBC SECTION |
| | 1804.2.2. |
| | |
| | 4) PLEASE REVISE CONSTRUCTION TYPE ON |
| | A4 TO TYPE VI. |
| | |
| | 5) SPECIFY THAT THE WWM FOR THE SLAB IS |
| | TO BE SUPPORTED AT A MAXIMUM OF 3 FEET |
| | PER FBC 1909.3. |
| | |
| | 6)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 7) SPECIFY ONE HOUR FIRE RATED GLASS |
| | BLOCK IS REQUIRED AT ZERO LOT LINE. |
| | REVISE GLASS BLOCK DETAIL TO SHOW A FIRE |
| | RATED ASSEMBLY. |
| | |
| | 8) PROVIDE A DETAIL OF THE 4X8 LINTEL |
| | ASSEMBLY AT ENTRY. |
| | |
| | 9) SPECIFY THAT THE GLASS BLOCK IN THE |
| | MASTER BATH IS REQUIRED TO HAVE A MIN. |
| | UNIFORM FACE THICKNESS OF 0.25 INCH. |
| | |
| | 10) INDICATE THE TYPE WELD, THICKNESS OF |
| | THE STEEL, ETC. FOR THE 2" STEEL HEADER |
| | IN THE DETAIL ON A8. |
| | |
| | 11) PROVIDE CALCULATIONS INDICATING THAT |
| | THE REQUIRED NET FREE VENTILATING AREA |
| | IS BEING PROVIDED. FBC 2309.7 |
| | |
| | 12) SPECIFY THE SIZE OF THE WASHERS USED |
| | ON THE TAPCON FASTENERS FOR THE GARAGE |
| | DOOR BUCKS ON A8. |
| | |
| | 13) REVISE THE SWING DOOR BUCK DETAIL ON |
| | A8 TO COMPLY WITH FBC 1707.4.4.2. |
| | |
| | 14) PROVIDE A STRUCTURAL DETAIL OF THE |
| | 3" DIAMETER STEEL BOLLARD IN THE GARAGE. |
| | |
| | 15) SPECIFY ON THE PLANS THAT THE DOOR |
| | BETWEEN THE GARAGE AND THE CONDITIONED |
| | SPACE IS A SOLID CORE AS REQUIRED BY |
| | FBC CHAPTER 13. |
| | |
| | 16) PROVIDE SPECIFICATIONS AND LISTING |
| | INFORMATION FOR THE ONE HOUR FIRE RATED |
| | GLASS BLOCK ASSEMBLIES. |
| | |
| | 17) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SINGLE FRENCH DOOR WITH DESIGN |
| | PRESSURES OF +46 & - 60.4 PSF |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |