| Plan Review Notes For Permit 02100040 |
| Permit Number |
02100040 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-23 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250-66 SHOWN AS #4. | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL "B". SIZE PER 250-122 | | | | | | 3)NOTE: PLEASE NOTE A PANEL "C" IS SHOWN | | | ON METER/MAIN COMBO AND NOT ON RISER | | | OR PLANS? PLEASE SHOW, CONDUIT,WIRE, | | | LOCATION ETC 215-5 | | | | | | 4)NOTE: PLEASE NOTE THAT PLANS SHOW A | | | SD IN KITCHEN. PLEASE NOTE SD IS NOT | | | PERMITTED IN KITCHEN PER NFPA-72 | | | 8-1.4.1.6 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|