| 2002-10-24 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGES |
| | TO PLANS,AND RESUBMIT FOR REVIEW: |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} THE RISER DIAGRAM DOES NOT SHOW THE |
| | MAIN DISCONNECT REQUIRED BY 230-70 NEC |
| | & 230-70(A) CWPB AMMENDMENTS. |
| | |
| | A) ALSO NOTE THAT IF THE MAIN IS TO BE |
| | LOCATED IN THE PANEL,THE #6 EQ. GND. |
| | MUST BE REMOVED PER 250-24(A)(1). |
| | |
| | 3} THE NOTE REGARDING LOAD CALCS SHOULD |
| | REFER TO 220-30 INSTEAD OF 230-30. |
| | |
| | 4} PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM PER 250-50(A),(B) & |
| | (C),REFERENCE FOOTER STEEL. |
| | |
| | 5} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210-12. |
| | |
| | 7} PLEASE NOTE KITCHEN COUNTERTOP |
| | RECEPTACLES MUST COMPLY WITH |
| | 210-8(A)(6)GFI'S. |
| | |
| | 8} NOTE GARAGE RECEPTACLES AS GFI PER |
| | 210-8(A)(2). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R.(BILL) TROBAUGH |
| | ELECTRICAL PLANS REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT. 8392 |