| Plan Review Notes For Permit 02100004 |
| Permit Number |
02100004 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-15 00:00:00 | UNSAT | | | ~~~~~ | | | PLEASE PROVIDE THE FOLLOWING FOR REVIEW. | | | | | | 1} THE NAMEPLATE RATING IN VOLTAGE AND | | | AMPERAGE OF THE FIXTURES TO BE USED. | | | | | | 2} THE LOAD ON THE EXISTING CIRCUIT THAT | | | IS INTENDED TO BE EXTENDED TO THE NEW | | | LIGHTS.ALSO THE SIZE OF THE OCP FOR | | | THAT CIRCUIT,SHOW SAME COMPLYING @ 125% | | | PER 215-2. | | | | | | 3} PLEASE NOTE THAT THE ENGINEERS TITLE | | | BLOCK MUST BE ACCOMPANIED BY A SEAL | | | PURSUANT TO 61G15-23.002 FAC.PLEASE | | | COMPLY WITH SAME ON THE PERMIT SET OF | | | PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|