| 2004-06-30 00:00:00 | REVISION FOR SHEETS ASP-1, A-203, A-204 |
| | & A-302, RE-SUBMITTED 6/25/04 (AMENDED |
| | IN RESPONSE TO 6/15/04 DENIAL OF THE |
| | REVISION ORIGINALLY SUBMITTED 6/8/04): |
| | |
| | 2) FBC* 1606.1CABANA ROOM WINDOW. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED |
| | SINCE THE LAST REVIEW.THE SIZE OF THE |
| | PROPOSED 7'-2" WIDE CABANA ROOM WINDOW |
| | EXCEEDS THE SIZE COVERED BY THE |
| | SUBMITTED PGT INDUSTRIES SINGLE HUNG |
| | WINDOW PRODUCT APPROVAL NOA# 02-0419.13. |
| | STRUCTURAL MULLIONS ARE REQUIRED. |
| | SUBMIT A PRODUCT APPROVAL FOR THE |
| | MULLIONS, OR SUBMIT ENGINEERING FOR |
| | MULLIONS. |
| | |
| | 4) FBC 2103.2.4SHEET A-203, NEW SITE |
| | WALL.THE WALL SHALL HAVE A MINIMUM OF |
| | 1#4 VERTICAL BAR AT 48" O.C. IN CONCRETE |
| | FILLED CELLS.AMEND THE PLAN. |
| | |
| | NOTE: |
| | THE REVISED SHEET A-204 DOES NOT INCLUDE |
| | THE GUARDRAIL STRENGTH PROVISO NOTE |
| | (COPY ATTACHED FOR EASE OF REFERENCE) |
| | THAT WAS ATTACHED TO THE PERMIT APPROVED |
| | COPY OF SHEET S204/SK3 AT THE TIME OF |
| | PERMIT ISSUE.AMEND THE PLAN BEFORE |
| | RE-SUBMITTING THE REVISION. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |