2004-06-30 00:00:00REVISION FOR SHEETS ASP-1, A-203, A-204
 & A-302, RE-SUBMITTED 6/25/04 (AMENDED
 IN RESPONSE TO 6/15/04 DENIAL OF THE
 REVISION ORIGINALLY SUBMITTED 6/8/04):
  
 2) FBC* 1606.1CABANA ROOM WINDOW.
 THIS COMMENT HAS NOT BEEN ADDRESSED
 SINCE THE LAST REVIEW.THE SIZE OF THE
 PROPOSED 7'-2" WIDE CABANA ROOM WINDOW
 EXCEEDS THE SIZE COVERED BY THE
 SUBMITTED PGT INDUSTRIES SINGLE HUNG
 WINDOW PRODUCT APPROVAL NOA# 02-0419.13.
 STRUCTURAL MULLIONS ARE REQUIRED.
 SUBMIT A PRODUCT APPROVAL FOR THE
 MULLIONS, OR SUBMIT ENGINEERING FOR
 MULLIONS.
  
 4) FBC 2103.2.4SHEET A-203, NEW SITE
 WALL.THE WALL SHALL HAVE A MINIMUM OF
 1#4 VERTICAL BAR AT 48" O.C. IN CONCRETE
 FILLED CELLS.AMEND THE PLAN.
  
 NOTE:
 THE REVISED SHEET A-204 DOES NOT INCLUDE
 THE GUARDRAIL STRENGTH PROVISO NOTE
 (COPY ATTACHED FOR EASE OF REFERENCE)
 THAT WAS ATTACHED TO THE PERMIT APPROVED
 COPY OF SHEET S204/SK3 AT THE TIME OF
 PERMIT ISSUE.AMEND THE PLAN BEFORE
 RE-SUBMITTING THE REVISION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS