2004-06-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 6/8/04 FOR SHEET
 A-203.
  
 1) FBC* 104.2.1WEST ELEVATION OF
 CABANA ROOM.SHEET A-302, ELEVATIONS,
 HAS NOT BEEN REVISED TO REFLECT THE
 PROPOSED CHANGES TO THE CABANA ROOM
 WINDOW.SUBMIT A REVISED ELEVATION.
  
 2) FBC* 1606.1THE SIZE OF THE PROPOSED
 7'-2" WIDE CABANA ROOM WINDOW EXCEEDS
 THE SIZE COVERED BY THE SUBMITTED PGT
 INDUSTRIES SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 02-0419.13.STRUCTURAL
 MULLIONS ARE REQUIRED.SUBMIT A PRODUCT
 APPROVAL FOR THE MULLIONS, OR SUBMIT
 ENGINEERING.
  
 3) FBC* 104.2.1SOUTH ELEVATION AND
 SECOND FLOOR PLAN. SHEET A-302 -
 ELEVATIONS, AND SHEET A-204 - SECOND
 FLOOR PLAN HAVE NOT BEEN REVISED TO
 REFLECT THE PROPOSED CHANGES TO THE
 COLUMN ARRANGEMENT.SUBMIT REVISED
 SHEETS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]