| 2003-06-23 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENT |
| | NUMBERING FOLLOWS ON FROM THE BUILDING |
| | PLAN REVIEW OF 5/19/03: |
| | |
| | 15) FBC 3401.7.1.2AREA OF ADDITION V'S |
| | AREA OF EXISTING BUILDING (NOTE: SEE |
| | COMMENT #19 BELOW FOR AN EXPLANATION OF |
| | THE EFFECTS OF THE CODE REVISIONS COMING |
| | INTO EFFECT JULY 1, 2003).IT IS NOTED |
| | THAT ON SHEETS ASP-1 AND A-203 THE AREA |
| | OF THE EXISTING BUILDING HAS NOW BEEN |
| | DECLARED AS 2680 S.F. (WAS 3872 S.F ON |
| | THE PREVIOUS REVISION OF THE PLANS). THE |
| | AREA OF THE ADDITION, AT 967 S.F., NOW |
| | EXCEEDS 25% OF THE EXISTING BUILDING |
| | AREA.BOTH THE EXISTING BUILDING AND |
| | THE ADDITION SHALL BE MADE TO COMPLY |
| | WITH ALL REQUIREMENTS OF FBC FOR A |
| | BUILDING OF A SIZE EQUAL TO THE COMBINED |
| | AREA AS FOLLOWS: |
| | |
| | 16) FBC 1005.4 EMERGENCY EGRESS WINDOWS. |
| | AMEND OR ANNOTATE THE PLANS TO SHOW THAT |
| | THE WINDOWS TO THE EXISTING BEDROOMS #2 |
| | AND #3 PROVIDE MINIMUM CLEAR OPENINGS OF |
| | 24" HIGH X 20" WIDE FOR SECONDARY EGRESS |
| | ALSO THE MINIMUM NET CLEAR OPENING SHALL |
| | BE 5.7 SQ FT. |
| | |
| | 17) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | THE SUBMITTED FORMS ARE FOR THE ADDITION |
| | ONLY.AS PER COMMENT #15 (ABOVE) THE |
| | WHOLE HOUSE SHALL BE SHOWN TO COMPLY BY |
| | SUBMITTAL OF CODE COMPLIANCE FORMS FOR |
| | THE WHOLE HOUSE. |
| | |
| | 18) FBC 1015.3STAIR GUARDRAIL.AMEND/ |
| | ANNOTATE THE PLANS TO SHOW THAT THE |
| | STAIR GUARDRAIL ON THE EXISTING STAIR IS |
| | AT LEAST 36" HIGH AND THE RAILS ARE |
| | SPACED SO THAT A 4" SPHERE CANNOT PASS |
| | THROUGH ANY OPENING UPTO A HEIGHT OF 34" |
| | |
| | 19) WITH REFERENCE TO COMMENT #15 ABOVE, |
| | NOTE THAT, AFTER THE JULY 1, 2003 |
| | REVISIONS TO THE FLORIDA BUILDING CODE |
| | COME INTO EFFECT, FBC 3701.7.1.2 WILL NO |
| | LONGER BE APPLICABLE TO R3 OCCUPANCIES |
| | (WHICH INCLUDES ONE AND TWO FAMILY |
| | DWELLINGS).FOR GROUP R3 OCCUPANCY THAT |
| | SECTION WILL BE REPLACED BY NEW SECTION |
| | FBC 3401.7.1.2, WHICH STATES THAT WHEN |
| | THE ADDITION CONSTITUTES 25% OR MORE OF |
| | THE AREA OF THE EXISTING BUILDING, THE |
| | ADDITION SHALL BE MADE TO COMPLY WITH |
| | THE CODE, AND THE EXISTING BUILDING |
| | SHALL COMPLY WITH THE FOLLOWING: |
| | A) G.F.C.I. OUTLETS SHALL BE INSTALLED |
| | WHERE REQUIRED BY THE CODE. |
| | B) SMOKE DETECTORS SHALL BE INSTALLED |
| | WHERE REQUIRED BY THE CODE. |
| | C) IN NO CASE SHALL THE EXISTING |
| | BUILDING AND THE ADDITION EXCEED |
| | THE SIZE/TYPE LIMITS OF TABLE 500. |
| | THESE, LESS RESTRICTIVE REQUIREMENTS ARE |
| | APPLICABLE TO ANY BUILDING PERMIT |
| | APPLICATION RECEIVED ON/AFTER |
| | JULY 1, 2003. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |