2003-05-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SUBMIT LOAD CALCULATIONS
 PER 220,215-5,FOR EXISTING LOADS AND
 ALL ADDED LOADS.
  
 3} PROVIDE A RISER DIAGRAM INDICATING
 ALL CONDUIT & CONDUCTOR SIZES.ALSO SHOW
 THE GROUNDING ELECTORDE SYSTEM
 COMPLYING WITH 250-50 & 250-66.
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE.(FOR THE CABANA ROOM).210-12.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.ON SCHEDULE.
  
 6} INDICATE THE OVER CURRENT PROTECTION
 IN THE METER/MAIN FOR THE EQUIPMENT IT
 FEEDS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718