| Plan Review Notes For Permit 02091769 |
| Permit Number |
02091769 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-09 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES TO | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE SUBMIT LOAD CALCULATIONS | | | PER 220,215-5,FOR EXISTING LOADS AND | | | ALL ADDED LOADS. | | | | | | 3} PROVIDE A RISER DIAGRAM INDICATING | | | ALL CONDUIT & CONDUCTOR SIZES.ALSO SHOW | | | THE GROUNDING ELECTORDE SYSTEM | | | COMPLYING WITH 250-50 & 250-66. | | | | | | 4} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE.(FOR THE CABANA ROOM).210-12. | | | | | | 5} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.ON SCHEDULE. | | | | | | 6} INDICATE THE OVER CURRENT PROTECTION | | | IN THE METER/MAIN FOR THE EQUIPMENT IT | | | FEEDS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|