Plan Review Notes
Plan Review Notes For Permit 02091769
Permit Number 02091769
Review Stop B
Sequence Number 2
Notes
Date Text
2003-05-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/5/02:
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.BEFORE A BUILDING PERMIT
 CAN BE ISSUED, THE SUBMITTED ENERGY CODE
 COMPLIANCE FORMS SHALL BE SIGNED BY THE
 BUILDING OWNER, THE OWNER'S ARCHITECT
 OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.ALSO THE
 PROJECT INFORMATION HAS NOT BEEN
 COMPLETED.ENTER THE NAME OF THE
 BUILDER, PERMITTING OFFICE (WEST PALM
 BEACH), JURISDICTION NUMBER (604700) AND
 PERMIT NUMBER (02091769).CORRECT THE
 PROJECT ADDRESS CITY TO READ 'WEST PALM
 BEACH' INSTEAD OF "PLM BCH CO".
  
 4) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT PRODUCT APPROVALS FOR THE NEW
 CEMENT TILE ROOFING, NEW AND REPLACEMENT
 WINDOWS, AND THE NEW GLAZED EXTERIOR
 DOORS.THE SPECIFICATION OF IMPACT
 RESISTANT GLAZING FOR BOTH THE NEW AND
 EXISTING WINDOWS IS NOTED.
  
 7) ANCHORS AND STRAPS.THE ADDITION OF
 ANCHOR REFERENCES ON THE PLANS IS NOTED
 BUT THE TYPE AND NUMBER OF ANCHOR
 FASTENERS TO THE TRUSSES JOISTS, BEAMS
 ETC SHALL BE SPECIFIED ON THE PLANS.
  
 11) FBC 2405.2SAFETY GLAZING FOR NEW
 EXTERIOR DOORS.THE GLASS IN THE NEW
 ALUMINUM CABANA BATH DOOR IS NOT SHOWN
 AS IMPACT RESISTANT ON SHEET A-203
 (FIRST FLOOR PLAN) OR SHEET A-302
 (ELEVATION).THIS GLASS IS IN A
 'HAZARDOUS LOCATION' AND IS REQUIRED TO
 BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 13) THE SUBMITTED NOTICE OF
 COMMENCEMENT IS MORE THAN ONE YEAR OLD
 AND HAS EXPIRED.A VALID RECORDED COPY
 OF THE NOTICE OF COMMENCEMENT MUST BE
 BE SUBMITTED BEFORE A BUILDING PERMIT
 CAN BE ISSUED.
  
 14) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN