Plan Review Notes
Plan Review Notes For Permit 02091769
Permit Number 02091769
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.1.2THE CHIMNEY IS SHOWN
 ON EACH OF THE EXISTING ELEVATIONS BUT
 IT IS OMITTED FROM THE PROPOSED
 ELEVATIONS.THERE ARE NO NOTES STATING
 THAT THE CHIMNEY IS TO BE REMOVED.
 CLARIFY/AMEND THE PLANS AS APPROPRIATE
 TO FULLY DESCRIBE THE SCOPE OF WORK.
 IS THE CHIMNEY TO BE REMOVED?
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS (FORM
 600C-01 SOUTH)
  
 4) SUBMIT PRODUCT APPROVALS FOR THE NEW
 CEMENT TILE ROOFING, NEW AND REPLACEMENT
 WINDOWS, AND THE NEW GLAZED EXTERIOR
 DOORS.THE SPECIFICATION OF IMPACT
 RESISTANT GLAZING FOR BOTH NEW WINDOWS
 AND THE REPLACEMENT OF EXISTING WINDOWS
 IS NOTED.
  
 5) FBC 1606.1.7WIND LOAD DESIGN
 INFORMATION.THE INFORMATION SHOWN ON
 THE PLANS IS NOTED, BUT FOR DESIGN OF
 EXTERIOR COMPONENTS AND CLADDING THE
 ROOF PRESSURES EXTRACTED FROM FBC TABLE
 1606.2B ARE FOR A ROOF ANGLE OF 30 TO 45
 DEGREES WHICH IS NOT CORRECT.AS THE
 ANGLE OF THE PROPOSED ROOF IS BETWEEN
 10 AND 30 DEGREES, IT WILL BE SUBJECTED
 TO GREATER NEGATIVE WIND PRESSURES IN
 ZONES 2 AND 3.AMEND THE EXTRACTS ON
 BOTH SHEET S-203 AND SHEET S-701, AND
 REVIEW THE DESIGN ACCORDINGLY.
  
 6) FBC 1606.2.3SHEET S-701.THE EDGE
 STRIP AND END ZONE DIAGRAM EXTRACTS FROM
 FBC FIGURE 1606.2(C) FOR COMPONENT AND
 CLADDING WIND LOAD ARE INCORRECT.
 ZONE 5 IS NOT SHOWN ON THE BUILDING
 ELEVATION, AND THE ZONES FOR HIPPED
 ROOFS HAVE BEEN INCORRECTLY LABELLED.
 AMEND THE PLANS.
  
 7) ANCHORS AND STRAPS.SHEETS S-202 AND
 S-203 DO NOT STATE THE UPLIFT AT THE
 TRUSS SUPPORTS AND DO NOT SPECIFY ANCHOR
 REFERENCES AT FLOOR FRAMING OR ROOF
 TRUSS SUPPORT LEVELS.ADD THE REQUIRED
 INFORMATION TO THE PLANS.
  
 8) WALL SECTION THROUGH LIBRARY.SHEET
 A-702, SECTION D SPECIFIES 'LSC18 STRAP'
 AT THE CABANA ROOM TRUSS SUPPORT.
 UNLIKE THE ANCHORS SPECIFIED ELSEWHERE
 ON THE PLANS, THIS IS NOT A SIMPSON
 REFERENCE.CLARIFY/AMEND THE REFERENCE
 AS APPROPRIATE.
  
 9) FBC* TABLE 2306.1THE ROOF SHEATHING
 FASTENER TYPE AND SPACING SHALL ADDED TO
 THE PLANS TO DEMONSTRATE COMPLIANCE WITH
 THIS CITY OF WPB AMENDMENT TO FBC 2001.
  
 10) FBC 2309.6ACCESS TO ATTIC SPACE.
 AMEND THE PLANS TO SHOW THE PROVISION OF
 AN OPENING, NOT LESS THAN 20"X 36", FOR
 EACH ATTIC SPACE THAT HAS A CLEAR HEIGHT
 OF 24" OR GREATER.
  
 11) FBC 2405.2THE GLAZING IN THE NEW
 ALUMINUM EXTERIOR DOORS IS IN A
 'HAZARDOUS LOCATION' AND IS REQUIRED TO
 BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 12) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499