| Plan Review Notes For Permit 02091705 |
| Permit Number |
02091705 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-22 00:00:00 | *********** NOTES REDLINED*********** | | | | | | 1)NOTE: MISSING EQUIPMENT GROUNDING | | | CONDUCTOR BETWEEN MAIN DISC AND PANEL. | | | SIZE PER 250-122 | | | | | | 2)NOTE: SD NOT PERMITTEDIN KITCHEN, | | | TO BE 3'MIN. NFPA-72 8-1.4.1.6 | | | | | | 3)NOTE: PLEASE NOTE CONDUIT BETWEEN MAIN | | | AND PANEL TO BE SIZED PER NEC TABLES | | | MIN 2". | | | | | | PLEASE REVISE PLANS BEFORE ROUGH. | | | IF THERE ARE NAY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|