| Plan Review Notes For Permit 02091693 |
| Permit Number |
02091693 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-02 00:00:00 | 1) PLEASE INDICATE IF THERE'S ANY FIRE | | | SEPARATION BETWEEN THE WAREHOUSE AND | | | SHOWROOM. | | | | | | 2) PLEASE EXPLAIN HOW EXITING WORKS FROM | | | THE WAREHOUSE AREA. | | | | | | 3) THE ELECTRICAL PLAN DISPLAYS ONLY ONE | | | EMERGENCY LIGHT IN THE WAREHOUSE. THERE | | | APPEARS TO BE NO EXIT SIGNS IN THE | | | WAREHOUSE. PLEASE ADVISE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096, EXT. 8497 | | | 835-2910 |
|