Plan Review Notes
Plan Review Notes For Permit 02091693
Permit Number 02091693
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-11 00:00:00THE PLANS INDICATE A MIXED OCCUPANCY
 USE.PROVIDE THE TWO HOUR FIRE RATED
 SEPARATION FOR THE GROUP M AND S2 USES
 IN ACCORDANCE WITH FBC 704.1 AND INSURE
 THAT THE EXISTING DEMISING WALL IS TWO
 HOUR RATED OR MODIFY AS NECESSARY.
  
 INDICATE ON THE PLANS THE TYPE OF
 BUSINESS AND THE NATURE AND QUANTITY OF
 THE COMMODITIES TO BE STORED ON THE
 PREMISES.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 PARTIONS AND THE OPENING PROTECTIVES.
 SEE FBC 701.2.
  
 SHOW A CONNECTION DETAIL FOR THE
 OVERHEAD DOOR TO BE INSTALLED AND
 PROVIDE A NOTICE OF ACCEPTANCE AND/OR
 TEST REPORT FROM A RECOGNIZED AGENCY
 FOR THE OVER HEAD DOOR.SHOW THE WIND
 PRESSURES FOR THE OPENING.
  
 SHEET A-3, SECTION A OPENING THROUGH
 EXISTING WALL, WHERE DOES THIS TAKE
 PLACE? WHAT IS THE HEADER SIZE?