| Plan Review Notes For Permit 02091693 |
| Permit Number |
02091693 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-11 00:00:00 | THE PLANS INDICATE A MIXED OCCUPANCY | | | USE.PROVIDE THE TWO HOUR FIRE RATED | | | SEPARATION FOR THE GROUP M AND S2 USES | | | IN ACCORDANCE WITH FBC 704.1 AND INSURE | | | THAT THE EXISTING DEMISING WALL IS TWO | | | HOUR RATED OR MODIFY AS NECESSARY. | | | | | | INDICATE ON THE PLANS THE TYPE OF | | | BUSINESS AND THE NATURE AND QUANTITY OF | | | THE COMMODITIES TO BE STORED ON THE | | | PREMISES. | | | | | | SHOW THE FIRE DESIGN NUMBER FOR THE | | | PARTIONS AND THE OPENING PROTECTIVES. | | | SEE FBC 701.2. | | | | | | SHOW A CONNECTION DETAIL FOR THE | | | OVERHEAD DOOR TO BE INSTALLED AND | | | PROVIDE A NOTICE OF ACCEPTANCE AND/OR | | | TEST REPORT FROM A RECOGNIZED AGENCY | | | FOR THE OVER HEAD DOOR.SHOW THE WIND | | | PRESSURES FOR THE OPENING. | | | | | | SHEET A-3, SECTION A OPENING THROUGH | | | EXISTING WALL, WHERE DOES THIS TAKE | | | PLACE? WHAT IS THE HEADER SIZE? |
|