| Plan Review Notes For Permit 02091658 |
| Permit Number |
02091658 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-30 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} THE CONDUCTOR SIZE REQUIRED BY NEC | | | 310-15(B)(6) FOR 400 AMPS FOR 400 MCM. | | | | | | A) 3-400 MCM IN A 2" PVC IS NOT | | | ALLOWED. SEE APPROPRIATE TABLE FOR THE | | | CONDUIT TYPE BEING USED. | | | | | | B) TABLE 210-66 LISTS 1/0 AS THE | | | GEC SIZE FOR 400 MCM. | | | | | | 2} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | THIS CAN BE BROUGHT IN AS A SUBMITTAL | | | OR FAXED TO ME,FILL OUT THE FORM IN | | | EITHER CASE (ATTACHED),AND KEEP A COPY | | | OF THE RATING AND ON THE | | | JOB FOR THE INSPECTOR.GET THIS | | | INFORMATION FROM FPL BEFORE INSPECTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 | | | FAX 561/653-2692 |
|