| Plan Review Notes For Permit 02091641 |
| Permit Number |
02091641 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT ME-4 GENERAL NOTES #1, CODE IN | | | EFFECT IS FBC-2001. | | | 2) SHT ME-4 PROVIDE MANUFACTURE CUT | | | SHEETS FOR INST-HOT. | | | 3) SHT ME-4 WATER RISER DIAGRAMS, AIR | | | CHAMBERS ARE NOT APPROVED. WATER HAMMER | | | ARRESTORS REQUIRED BY SECTION 604.9 | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE" NOT AT THE TOP OF THE | | | DROP IN CEILING AS SHOWN PER PDI-WH 201 | | | AND MANUFACTURE INSTALLATION INSTRUCTION | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|