Plan Review Notes
Plan Review Notes For Permit 02091632
Permit Number 02091632
Review Stop P
Sequence Number 3
Notes
Date Text
2003-01-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEWS: PLEASE ROUTE
 PLANS TO THE DEPT. OF BUSINESS REGULAT-
 ION, HOTEL & RESTURANT DIVISION. (954)
 956-5692. PRIOR TO RESUBMITTING FOR PLAN
 REVIEW AT CITY OF WEST PALM BEACH. PLANS
 SHALL BE STAMPED AND WORK SHEET ATTACHED
 2) FROM PREVIOUS REVIEWS: PLEASE CONTACT
 RODNEY COMPO ENVIRONMENTAL COMPLIANCE,
 AT (561) 837-4074. MINIMUM 750 GALLON
 GREASE TRAP REQUIRED. WASTE ORD. #2938-
 96.
 3) FROM PREVIOUS REVIEWS: SHT P-1 & SHT
 P-2 SEPARATE GREASE LINE REQUIRED.
 4) FROM PREVIOUS REVIEWS: THERMAL EXPAN-
 SION CONTROL IS REQUIRED AT WATER HEATER
 DETAIL SHT P-2. SEC 607.3.2- AN EXPAN-
 SION TANK IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377