| Plan Review Notes For Permit 02091632 |
| Permit Number |
02091632 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-01-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) FROM PREVIOUS REVIEWS: PLEASE ROUTE | | | PLANS TO THE DEPT. OF BUSINESS REGULAT- | | | ION, HOTEL & RESTURANT DIVISION. (954) | | | 956-5692. PRIOR TO RESUBMITTING FOR PLAN | | | REVIEW AT CITY OF WEST PALM BEACH. PLANS | | | SHALL BE STAMPED AND WORK SHEET ATTACHED | | | 2) FROM PREVIOUS REVIEWS: PLEASE CONTACT | | | RODNEY COMPO ENVIRONMENTAL COMPLIANCE, | | | AT (561) 837-4074. MINIMUM 750 GALLON | | | GREASE TRAP REQUIRED. WASTE ORD. #2938- | | | 96. | | | 3) FROM PREVIOUS REVIEWS: SHT P-1 & SHT | | | P-2 SEPARATE GREASE LINE REQUIRED. | | | 4) FROM PREVIOUS REVIEWS: THERMAL EXPAN- | | | SION CONTROL IS REQUIRED AT WATER HEATER | | | DETAIL SHT P-2. SEC 607.3.2- AN EXPAN- | | | SION TANK IS REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|