| Date |
Text |
| 2002-12-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) FROM PREVIOUS REVIEW, PLEASE ROUTE |
| | PLANS TO THE DEPT. OF BUSINESS REGULAT- |
| | ION, HOTEL & RESTURANT DIVISION (954) |
| | 956-5692 PRIOR TO RE-SUBMITTING FOR PLAN |
| | REVIEW AT THE CITY OF WPB. |
| | 2) FROM PREVIOUS REVIEW, PLEASE CONTACT |
| | RODNEY COMPO ENVIRONMENTAL COMPLIANCE |
| | MANAGER FOR SIZING OF GREASE TRAP. |
| | 3) FROM PREVIOUS REVIEW, SHT P-1 MINIMUM |
| | FACILITIES TABLE 403.1 REQUIRE A DRINK- |
| | ING FOUNTAIN. |
| | 4) FROM PREVIOUS REVIEW, SHT P-1 WATER |
| | FILTER SHALL BE NSF APPROVED. PLEASE |
| | SUBMIT MANUF. INFO. |
| | 5) FROM PREVIOUS REVIEW, SHT P-1 PLUMB- |
| | ING NOTES #5, AIR CHAMBERS ARE NOT APP- |
| | ROVED. PLEASE DELETE REFERENCE FROM NOTE |
| | 6) FROM PREVIOUS REVIEW, SHT P-1 SEPAR- |
| | ATE GREASE LINE REQUIRED. |
| | 7) FROM PREVIOUS REVIEW, SHT P-1 BACK- |
| | FLOW IS REQUIRED FOR WATER SERVICE. MAX- |
| | IMUM 4' FINISHED FLOOR. ALSO SHOW ON |
| | RISER DIAGRAM SHT P-2. |
| | 8) FROM PREVIOUS REVIEW, THERMAL EXPAN- |
| | SIONCONTROL IS REQUIRED AT WATER HEATER |
| | DETAIL SHT P-2. SEC 607.3.2 |
| | 9) FROM PREVIOUS REVIEW, SHT P-2 SANIT- |
| | ARY - GREASE WASTE RISER DIAGRAM, SEPAR- |
| | ATE GREASE LINE REQUIRED. |
| | 10) NEW NOTE: WHEN ADDRESSING PLAN RE- |
| | VIEW COMMENTS, A TRANSMITTAL LETTER |
| | LISTING ORIGINAL REVIEW COMMENT NUMBER |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OF SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND. |
| | THIS WILL HELP EXPEDITE YOUR PERMIT. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |