Plan Review Notes
Plan Review Notes For Permit 02091632
Permit Number 02091632
Review Stop P
Sequence Number 2
Notes
Date Text
2002-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, PLEASE ROUTE
 PLANS TO THE DEPT. OF BUSINESS REGULAT-
 ION, HOTEL & RESTURANT DIVISION (954)
 956-5692 PRIOR TO RE-SUBMITTING FOR PLAN
 REVIEW AT THE CITY OF WPB.
 2) FROM PREVIOUS REVIEW, PLEASE CONTACT
 RODNEY COMPO ENVIRONMENTAL COMPLIANCE
 MANAGER FOR SIZING OF GREASE TRAP.
 3) FROM PREVIOUS REVIEW, SHT P-1 MINIMUM
 FACILITIES TABLE 403.1 REQUIRE A DRINK-
 ING FOUNTAIN.
 4) FROM PREVIOUS REVIEW, SHT P-1 WATER
 FILTER SHALL BE NSF APPROVED. PLEASE
 SUBMIT MANUF. INFO.
 5) FROM PREVIOUS REVIEW, SHT P-1 PLUMB-
 ING NOTES #5, AIR CHAMBERS ARE NOT APP-
 ROVED. PLEASE DELETE REFERENCE FROM NOTE
 6) FROM PREVIOUS REVIEW, SHT P-1 SEPAR-
 ATE GREASE LINE REQUIRED.
 7) FROM PREVIOUS REVIEW, SHT P-1 BACK-
 FLOW IS REQUIRED FOR WATER SERVICE. MAX-
 IMUM 4' FINISHED FLOOR. ALSO SHOW ON
 RISER DIAGRAM SHT P-2.
 8) FROM PREVIOUS REVIEW, THERMAL EXPAN-
 SIONCONTROL IS REQUIRED AT WATER HEATER
 DETAIL SHT P-2. SEC 607.3.2
 9) FROM PREVIOUS REVIEW, SHT P-2 SANIT-
 ARY - GREASE WASTE RISER DIAGRAM, SEPAR-
 ATE GREASE LINE REQUIRED.
 10) NEW NOTE: WHEN ADDRESSING PLAN RE-
 VIEW COMMENTS, A TRANSMITTAL LETTER
 LISTING ORIGINAL REVIEW COMMENT NUMBER
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OF SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND.
 THIS WILL HELP EXPEDITE YOUR PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377