Plan Review Notes
Plan Review Notes For Permit 02091632
Permit Number 02091632
Review Stop P
Sequence Number 1
Notes
Date Text
2002-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING.
  
 1) PLEASE ROUTE PLANS TO THE DEPT. OF
 BUSINESS REGULATION, HOTEL & RESTURANT
 DIVISION (954) 956-5692 PRIOR TO RE-SUB-
 MITTING FOR PLAN REVIEW AT CITY WPB.
 2) PLEASE CONTACT RODNEY COMPO ENVIRON-
 MENTAL COMPLIANCE MANAGER FOR SIZING OF
 GREASE TRAP.
 3) SHT P-1 MINIMUM FACILITIES TABLE
 407.3.1 REQUIRES A DRINKING FOUNTAIN.
 4) SHT P-1, WATER FILTER SHALL BE NSF
 APPROVED. PLEASE PROVIDE MANUF. INFO.
 5) SHT P-1 DOMESTIC WATER PIPING CALLS
 FOR GALVANIZED PIPE. ENGINEER SAYS THAT
 COPPER WILL BE USED. (SEE NOTE #3 UNDER
 PIPING MATERIALS). PLEASE CHANGE NOTES
 #1 & #2 FROM GALV. TO COPPER.
 6) SHT P-1 PLUMBING NOTES #5, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE FROM NOTES.
 7) SHT P-1 SEPARATE GREASE LINE REQUIRED
 8) SHT P-1 BACKFLOW IS REQUIRED FOR
 WATER SERVICE. MAXIMUM 4' ABOVE FINISHED
 FLOOR. ALSO SHOW ON WATER RISER DIAGRAM
 SHT P-2.
 9) SHT P-2 WATER HEATER DETAIL, PAN
 DRAIN/RELIEF VALVE DRAIN (T/P) SHALL
 DRAIN INTO A FLOOR SINK. FLOOR DRAIN NOT
 AN INDIRECT WASTE RECEPTOR. - THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION
 607.3.2
 10) SHT P-2 SANITARY - GREASE WASTE
 RISER DIAGRAM, SEPARATE GREASE LINE
 REQUIRED.
 11) HEALTH DEPT. REQUIREMENT - 140 DEGR-
 EE WATER REQUIRED FOR 3 COMPARTMENT SINK
 AND JANITOR SINK. - MIXING VALVE REQ-
 UIRED FOR 110 DEGREE WATER FOR OTHER
 FIXTURES REQUIRING HOT WATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved