2002-10-25 00:00:00DENIED:
  
 PLEASE PROVIDE ENERGY & MANUAL J CALCS.
  
 PLAN SHEET M-2 INDICATES CONDENSER UNIT
 STAND AS BEING 30" FROM ROOF SURFACE TO
 THE BOTTOM OF THE SUPPORT RAIL.SEE
 ATTACHED TABLE (1511.7) OF THE FLORIDA
 BUIDLING CODE FOR THE PROPER HEIGHT
 REQUIREMENT.
  
 SEPARATE PERMIT REQUIRED FOR THE
 FOLLOWING:
  
 WALK-IN COOLERS OR FREEZERS
 HOOD & FIRE SUPRESSION (IF APPLICABLE)
 GAS
  