| Plan Review Notes For Permit 02091632 |
| Permit Number |
02091632 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-25 00:00:00 | DENIED: | | | | | | PLEASE PROVIDE ENERGY & MANUAL J CALCS. | | | | | | PLAN SHEET M-2 INDICATES CONDENSER UNIT | | | STAND AS BEING 30" FROM ROOF SURFACE TO | | | THE BOTTOM OF THE SUPPORT RAIL.SEE | | | ATTACHED TABLE (1511.7) OF THE FLORIDA | | | BUIDLING CODE FOR THE PROPER HEIGHT | | | REQUIREMENT. | | | | | | SEPARATE PERMIT REQUIRED FOR THE | | | FOLLOWING: | | | | | | WALK-IN COOLERS OR FREEZERS | | | HOOD & FIRE SUPRESSION (IF APPLICABLE) | | | GAS | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|