| Plan Review Notes For Permit 02091632 |
| Permit Number |
02091632 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-07 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SHOW SIGN CIRCUIT REQ`D | | | PER 600-5 | | | | | | 2)NOTE: PLEASE CLARIFY SHOW WINDOW | | | OUTLETS PER 210-62 | | | | | | 3)NOTE: PLEASESHOW ALL CONTINUOUS LOAD | | | -S AT 125%. 215-3/230-42 | | | | | | 4)NOTE: PLEASE CLARIFY METHOD OF | | | EQUIPMENT GROUDING BETWEEM MAIN DISC AND | | | PANEL "B" AND PANEL "B AND PANEL "A". | | | EMT? PVC? PLEASE SIZE PER 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | PLEASE SEE ANY FIRE REVIEW COMMENTS THAT | | | MAY AFFECT ELECTRICAL PLANS. |
|