Plan Review Notes
Plan Review Notes For Permit 02091632
Permit Number 02091632
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-07 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SHOW SIGN CIRCUIT REQ`D
 PER 600-5
  
 2)NOTE: PLEASE CLARIFY SHOW WINDOW
 OUTLETS PER 210-62
  
 3)NOTE: PLEASESHOW ALL CONTINUOUS LOAD
 -S AT 125%. 215-3/230-42
  
 4)NOTE: PLEASE CLARIFY METHOD OF
 EQUIPMENT GROUDING BETWEEM MAIN DISC AND
 PANEL "B" AND PANEL "B AND PANEL "A".
 EMT? PVC? PLEASE SIZE PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE SEE ANY FIRE REVIEW COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.