Plan Review Notes
Plan Review Notes For Permit 02091622
Permit Number 02091622
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-01 00:00:00CHECKLIST:
 1-NEED TO PROVIDE RECORDED NOTICE OF
 COMMENCEMENT.
 2-BRING PLANS TO PALM BEACH COUNTY AFTER
 THEY ARE REVISED BY THE DESIGNER TO
 VERIFY IF IMPACT FEES ARE OWED. BRING
 BACK STAMPED DWGS AND PAID RECEIPT.
 3-FLOOR PLANS AND WALL SECTION DON'T
 MATCH. PLANS SHOW CONCRETE BLOCK AND
 WALL SECTION SHOW WOOD FRAMING. REVISE
 4-CLARIFY CONNECTION AT UNION OF NEW
 ROOF TO EXISTING ONE. CONNECTOR SHOWN
 IS FOR EXISTING ROOF TRUSSES OR FOR
 NEW JOISTS?. SEE SIMPSON CATALOGUE FOR
 PROPER UPLIFT CONNECTOR.
 PROVIDE ENGINEERING CALCULATIONS FOR
 CONNECTOR VALUES NOT PUBLISHED IN THE
 SIMPSON CATALOGUE. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS. NOTE: SEE PRODUCT
 APPROVALS FOR SIZE OF BUCK REQUIRED
 AND SECTION 1707.4.4.2 FBC 2001 FOR
 BUCK REQUIREMENTS.
 6-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS: PRODUCT APPROVAL AND INSTA-
 LLATION SCHEDULE. SEE CITY SAMPLE.
 NOTE: NEED 2 COPIES.
 7-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 FOR: A)FLAT ROOF SYSTEM TO BE USED.
 B)EXTERIOR SWING DOOR (NEED TWO COPIES.
 ONLY ONE WAS SUBMITTED)
 C)SINGLE HUNG WINDOWS. DRAWINGS ARE NOT
 LEGIBLE.
 D)SLIDING GLASS DOOR DRAWINGS ARE NOT
 LEGIBLE.