| Plan Review Notes For Permit 02091565 |
| Permit Number |
02091565 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-17 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1)FBC 13-103.0THE SUBMITTED ENERGY | | | CODE COMPLIANCE FORMS SHALL BE COMPLETED | | | BY ENTERING: | | | - THE ADDRESS | | | - THE PERMIT NUMBER | | | - THE PERMITTING OFFICE (CITY OF WPB) | | | - THE JURISDICTION NUMBER (604700) | | | - THE CLIMATE ZONE IS 8 | | | | | | 2) THE DRAWING SHEETS SUBMITTED WITH THE | | | SINGLE HUNG WINDOW PRODUCT APPROVAL | | | NOA# 98-1222.02 ARE POOR QUALITY REDUCED | | | COPIES WHICH CANNOT BE READ.SUBMIT | | | TWO LEGIBLE COPIES OF THE DRAWING SHEETS | | | | | | 3) SHEET A-02, FOUNDATION PLAN.DUE TO | | | COPY SIZE AND FONT TYPE USED, THE COLUMN | | | SCHEDULE AND THE NOTE BELOW THE FOOTING | | | SCHEDULE CANNOT BE READ.ALTER THE FONT | | | AND SUBMIT TWO LEGIBLE COPIES OF | | | SHEET A-02. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|