| Date |
Text |
| 2002-10-29 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) STRUCTURE IS LOCATEDIN AN "AO" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 3) ON SHEET A5 THERE IS A DETAIL TAG FOR |
| | 1 ON A8. HOWEVER THERE IS NO SHEET A8. |
| | PLEASE CORRECT. |
| | |
| | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | PLEASE INCLUDE ALL OF THIS REQUIRED |
| | INFORMATION ON THE PLANS. |
| | |
| | 5) NUMBER 11 OF THE PLAN NOTES ON SHEET |
| | C1 STATES THAT HURRICANE PANELS ARE |
| | REQUIRED IN HVHZ AREA. THE CITY OF WPB |
| | IS NOT LOCATED IN A HIGH VELOCITY |
| | HURRICANE ZONE, HOWEVER, IMPACT |
| | PROTECTION IS REQUIRED. PLEASE REVISE. |
| | |
| | 6)THE PLANS DO NOT INDICATE THE LOCATION |
| | OF THE ROOF DIAPHRAGM NAILING ZONES 1,2 |
| | & 3 THAT ARE LISTED IN THE DIAPHRAGM |
| | SCHEDULE AND BRACING LEGEND ON A6. |
| | |
| | 7) THERE IS NO TRUSS CONNECTOR SCHEDULE |
| | GIVEN TO CORRESPOND WITH THE CONNECTOR |
| | DESIGNATIONS ON A6. |
| | |
| | 8)THE KEY PLAN AND INSTALLATION SCHEDULE |
| | FOR THE STORM PANELS LIST INCORRECT |
| | OPENING SIZES FOR #S 2,3 & 13. PLEASE |
| | CORRECT. |
| | |
| | 9) THE GLASS BLOCK AT THE MASTER BATH |
| | TUB IS REQUIRED TO HAVE A MINIMUM |
| | UNIFORM FACE THICKNESS OF 0.25 INCH PER |
| | FBC 2405.2.1 AND 2405.2.2(5). |
| | |
| | 10) THE FBC SEC.1707.4.4.2 REQUIRES |
| | WINDOW AND DOOR ASSEMBLIES WITH BUCKS |
| | LESS THAN 1-1/2" THICK TO BE ANCHORED |
| | THROUGH THE BUCK TO THE ROUGH OPENING |
| | SUBSTRATE. |
| | |
| | 11) THE SITE SPECIFIC PRODUCT APPROVAL |
| | FORMS REQUIRE THE EMBOSSED SEAL OF THE |
| | DESIGNER OF RECORD IN ADDITION TO HIS |
| | SIGNATURE. |
| | |
| | 12) THERE WAS NO SITE SPECIFIC PRODUCT |
| | APPROVAL FORM SUBMITTED WITH THE |
| | UNCLIPPED VERTICAL MULLION DRAWINGS. |
| | |
| | 13) THE DIMENSIONS GIVEN IN THE DRAWINGS |
| | FOR THE DESIGNER WINDOWS DO NOT |
| | CORRESPOND WITH SEVERAL OF THE FIXED |
| | GLASS WINDOWS SHOWN ON THE PLANS. PLEASE |
| | REVIEW AND REVISE FOR THE SIZES ON THE |
| | PLANS. CHECK TO BE SURE THAT THE WIND- |
| | LOAD PRESSURES ARE ADEQUATE. |
| | |
| | 14) PROVIDE PRODUCT APPROVAL FOR |
| | HORIZONTAL STRUCTURAL MULLIONS. |
| | |
| | 15) PLEASE INSERT REVISED PAGES INTO THE |
| | PLANS. RETURN OLD PLANS TO EXPEDIATE |
| | PLAN REVIEW. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |