2002-10-07 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE/CLARIFY EXISTING
 SERVICE SHOWS FEED COMING FROM EXISTING
 100A PANEL GOING THROUGH METER AND THEN
 OUT TO BLDG. PLEASE NOTE MIXING LINE
 AND LOAD IN METER NOT PERMITTED. 215-5
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR EXISTING 100A PANEL. PLEASE SHOW
 SIZE OF OCP TO FEED MAINT BLDG.
 215-5
 3)NOTE: PLEASE NOTE NO INFORMATION SHOWN
 FOR NEW DISC AND PANEL AT DETACHED BLDG.
 215-5
 4)NOTE: PLEASE NOTE NO GROUNDING SYSTEM
 SHOWN AT DETACHED BLDG. 250-31
  
 5)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE W/ A SUBMITTED PANEL
 SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  