| 2002-10-07 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE/CLARIFY EXISTING | | | SERVICE SHOWS FEED COMING FROM EXISTING | | | 100A PANEL GOING THROUGH METER AND THEN | | | OUT TO BLDG. PLEASE NOTE MIXING LINE | | | AND LOAD IN METER NOT PERMITTED. 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | FOR EXISTING 100A PANEL. PLEASE SHOW | | | SIZE OF OCP TO FEED MAINT BLDG. | | | 215-5 | | | 3)NOTE: PLEASE NOTE NO INFORMATION SHOWN | | | FOR NEW DISC AND PANEL AT DETACHED BLDG. | | | 215-5 | | | 4)NOTE: PLEASE NOTE NO GROUNDING SYSTEM | | | SHOWN AT DETACHED BLDG. 250-31 | | | | | | 5)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE W/ A SUBMITTED PANEL | | | SCHEDULE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|