| 2003-01-07 00:00:00 | SECOND PLAN REVIEW FOR FOUNDATION PERMIT |
| | ONLY, NOT A PERMIT APPLICATION. |
| | |
| | RE: M. A. SUAREZ INSPECTION PLAN DATED |
| | 12/10/02. |
| | |
| | THE THRESHOLD INSPECTION PLAN IS NOT |
| | COMPLETE.PART A SCOPE OF WORK |
| | INCORPORATES SPECIFICATIONS AND OTHER |
| | ADDENDA THAT ARE NOT PROVIDED FOR CODE |
| | COMPLIANCE REVIEW. |
| | |
| | ITEM VI OF PART A, LAST PARAGRAPH |
| | RELIEVES RESPONSIBILITY OF COMPLETE |
| | INSPECTION OF CONCRETE TO AN UNDEFINED |
| | "LENGTH OF TIME" WHICH IS NOT AN |
| | ACCEPTABLE METHOD OF INSPECTION. |
| | |
| | SAME PARAGRAPH EXHORTS COMPLIANCE WITH |
| | THE "OFFICIAL CONTRACT DOCUMENTS RATHER |
| | THAN APPLICABLE CODES" AND IS FURTHER |
| | COMPLICATED BY REFERENCE TO THE 1994 |
| | SOUTH FLORIDA BUILDING CODE. |
| | |
| | PREVIOUS PAID PLAN REVIEW COMMENTS FOR |
| | BOTH THE BUILDING AND THE SEPARATE |
| | FOUNDATION HAVE NOT BEEN SATISFACTORILY |
| | ADDRESSED. |
| | |
| | QUESTIONS AS TO FOUNDATIONS IN THE |
| | PUBLIC RIGHT OF WAY ON THE NORTH AND |
| | WEST SIDES, HIBISCUS ST. AND DIXIE HWY. |
| | HAVE NOT BEEN CLARIFIED.WHERE ARE THE |
| | DIMENSIONS FOR THE FOOTINGS AND COLUMNS |
| | NORTH OF AND PARALLEL WITH GRID LINE P |
| | AND THOSE WEST OF AND PARALLEL WITH |
| | GRID LINE N.1? |
| | |
| | THE HANDICAP RAMP HAVING A LOCUS IN THE |
| | GRID LINES MADE BY H AND N.4 AS SHOWN |
| | ON SHEETS S.03 DATED 12/10/02 AND A.09 |
| | DATED 12/10/02 APPEARS TO HAVE LANDINGS |
| | THAT DO NOT COMPLY WITH THE FBC AS |
| | PREVIOUSLY NOTED.MORE SPECIFICALLY, |
| | THE 72" LENGTH AT THE BOTTOM AND |
| | MANEUVERING CLEARANCE AT THE DOOR AT |
| | THE TOP. FBC 11-4.8.4. |
| | |
| | FULL HANDICAP SITE ACCESSIBILITY AS |
| | PREVIOUSLY REQUESTED IS STILL NOT |
| | READILY DISCERNIBLE.THE KEITH AND |
| | BALLBE, INC SITE IMPROVEMENTS PLANS |
| | TOGETHER WITH WARREN MCCORMICK |
| | LANDSCAPE ARCHITECTURE,AND THE COHEN |
| | FREEMAN, ENCINOSA PLANS, DO NOT PROVIDE |
| | CONGRUENT DESIGN INFORMATION. |
| | |
| | PLEASE NOTE THAT THESE PLAN REVIEW |
| | COMMENTS, BASED ON INFORMATION |
| | AVAILABLE TO DATE, ARE DIRECTED TO A |
| | PROPOSED FOUNDATION BUILDING PERMIT |
| | ONLY.THERE ARE SIGNIFICANT CODE |
| | DISCREPANCIES STILL OUTSTANDING THAT |
| | MUST BE RESOLVED BEFORE A COMPLETE |
| | BUILDING CONSTRUCTION PERMIT WILL BE |
| | ISSUED. |