| 2002-10-25 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. |
| | |
| | A FOUNDATION PERMIT IS NOT FEASIBLE |
| | SINCE THE PLANS PRESENTED TO DATE HAVE |
| | A NUMBER OF CODE INFRACTIONS.THE |
| | PREVIOUS REVIEWS FOR THE COMPLETE |
| | BUILDING SHOWED CONFLICTS WITH THE |
| | HEIGHT OF THE BUILDING AND SITE |
| | TOPOGRAPHY WHICH HAVE NOT BEEN |
| | ADDRESSED. |
| | |
| | THE FOUNDATION STRUCTURE ON THE NORTH |
| | SIDE OF GRID LINE P ENCROACHES INTO THE |
| | PUBLIC RIGHT OF WAY APPROXIMATELY SEVEN |
| | FEET AND IS EXPRESSLY PROHIBITTED BY |
| | FBC 3206.1.1 AND FBC 3207.2.PLEASE |
| | REVISE AS NECESSARY PRIOR TO PERMIT |
| | APPLICATION. |
| | |
| | A THRESHOLD INSPECTION PLAN IN |
| | ACCORDANCE WITH FLORIDA STATUTES 553.71 |
| | REQUIRED AS WELL AS DEMONSTRATON OF THE |
| | OTHER CRITERIA CONTAINED THEREIN. |
| | |
| | SHEET S-01 CONTAINS A STATEMENT |
| | "HORIZONTAL LOADS ARE CONSIDERED IN |
| | ACCORDANCE WITH ASCE 7-98".CITING THE |
| | CODE WHOLLY OR IN PART IS NOT A |
| | SUBSTITUTE FOR SPECIFIC DESIGN |
| | INFORMATION.SEE FBC 104.2.1 AND |
| | INCLUDE ALL OF THE CRITERIA SET OUT IN |
| | FBC 104.3.1.1 WITH THE PERMIT |
| | APPLICATION. |
| | |
| | THERE ARE NO VALID SPECIFICATIONS FOR |
| | THIS PROJECT. |
| | |
| | THE SITE TOPOGRAPHY INFORMATION, OR LACK |
| | THEREOF, WOULD EFFECT THE ESTABLISHMENT |
| | OF THE SEVERAL FOOTING HEIGHTS.THERE |
| | WERE SOME QUESTIONS FOR THE HC RAMP |
| | ALONG GRID LINES H & N.4, AND OVERALL |
| | BUILDING SITE ACCESSIBILITY NOT YET |
| | RESOLVED AS WELL AS THE HIGHEST |
| | OCCUPIABLE FLOOR ABOVE FIRE DEPARTMENT |
| | VEHICLE ACCESS.THIS INFORMATION |
| | SHOULD ACCOMPANY ANY PERMIT |
| | APPLICATIONS. |
| | |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |