Notes
Date Text
2002-10-25 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
  
 A FOUNDATION PERMIT IS NOT FEASIBLE
 SINCE THE PLANS PRESENTED TO DATE HAVE
 A NUMBER OF CODE INFRACTIONS.THE
 PREVIOUS REVIEWS FOR THE COMPLETE
 BUILDING SHOWED CONFLICTS WITH THE
 HEIGHT OF THE BUILDING AND SITE
 TOPOGRAPHY WHICH HAVE NOT BEEN
 ADDRESSED.
  
 THE FOUNDATION STRUCTURE ON THE NORTH
 SIDE OF GRID LINE P ENCROACHES INTO THE
 PUBLIC RIGHT OF WAY APPROXIMATELY SEVEN
 FEET AND IS EXPRESSLY PROHIBITTED BY
 FBC 3206.1.1 AND FBC 3207.2.PLEASE
 REVISE AS NECESSARY PRIOR TO PERMIT
 APPLICATION.
  
 A THRESHOLD INSPECTION PLAN IN
 ACCORDANCE WITH FLORIDA STATUTES 553.71
 REQUIRED AS WELL AS DEMONSTRATON OF THE
 OTHER CRITERIA CONTAINED THEREIN.
  
 SHEET S-01 CONTAINS A STATEMENT
 "HORIZONTAL LOADS ARE CONSIDERED IN
 ACCORDANCE WITH ASCE 7-98".CITING THE
 CODE WHOLLY OR IN PART IS NOT A
 SUBSTITUTE FOR SPECIFIC DESIGN
 INFORMATION.SEE FBC 104.2.1 AND
 INCLUDE ALL OF THE CRITERIA SET OUT IN
 FBC 104.3.1.1 WITH THE PERMIT
 APPLICATION.
  
 THERE ARE NO VALID SPECIFICATIONS FOR
 THIS PROJECT.
  
 THE SITE TOPOGRAPHY INFORMATION, OR LACK
 THEREOF, WOULD EFFECT THE ESTABLISHMENT
 OF THE SEVERAL FOOTING HEIGHTS.THERE
 WERE SOME QUESTIONS FOR THE HC RAMP
 ALONG GRID LINES H & N.4, AND OVERALL
 BUILDING SITE ACCESSIBILITY NOT YET
 RESOLVED AS WELL AS THE HIGHEST
 OCCUPIABLE FLOOR ABOVE FIRE DEPARTMENT
 VEHICLE ACCESS.THIS INFORMATION
 SHOULD ACCOMPANY ANY PERMIT
 APPLICATIONS.
  
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.