| Plan Review Notes For Permit 02091413 |
| Permit Number |
02091413 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-01 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND MAKE ANY NECESSARY | | | CHANGES ON THE PLANS. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} THE RISER DIAGRAM SHOWS AN EXISTING | | | METER BUT THE NOTE AT THE METER | | | LOCATION INDICATE A NEW METER BEING | | | RELOCATED,PLEASE CLARIFY. | | | | | | 3} THE NOTE ON THE GROUNDING ELECTRODE | | | SYSTEM IS UNACCEPTABLE FOR | | | REVIEW.PLEASE PROVIDE DETAILS. | | | | | | 4} THE NOTE ABOUT THE SERVICE CONDUIT | | | BEING ROUTED IN THE CRAWL SPACE IS IN | | | VIOLATION OF ARTICLE 230-6 NEC AND | | | 230-70(A) WEST PALM BEACH AMMENDMENTS. | | | IN EITHER CASE A MAIN DISCONNECT WOULD | | | BE REQUIRED PER 225-31 & 225-32 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|