2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-3 DETAIL D, HDCP SINK SHALL BE
 34" MAX PER 11-4.24.2
 2) SHT M-1, PLEASE PROVIDE A WATER RISER
 DIAGRAM. IF WATER HAMMER ARRESTOR IS
 USED, LOCATE NEAR FIXTURE NOT IN CEILING
 AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377