| Plan Review Notes For Permit 02091401 |
| Permit Number |
02091401 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-24 00:00:00 | 1) PLANS DO NOT CONTAIN CITY PLACE | | | CONSTRUCTION APPROVAL STAMP. | | | | | | 2) SEPARATE FIRE ALARM PANEL SHOWN | | | ON THE PLANS WILL NOT BE ALLOWED TO | | | BE INSTALLED. FIRE ALARM EQUIPMENT FOR | | | SPACE MUST BE CONNECTED TO THE BASE | | | BUILDING'S FIRE ALARM SYSTEM. | | | | | | 3) PLEASE INDICATE ON THE PLANS ANY | | | TENANT DEMISING WALLS. | | | | | | 4) FIRE SPRINKLER HEADS ARE REQUIRED | | | THROUGHOUT INCLUDING BATHROOM AND | | | ENTRY FOYER. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|