Plan Review Notes
Plan Review Notes For Permit 02091401
Permit Number 02091401
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-26 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO BE
 STAMPED BY CITY PLACE FOR CONSTRUCTION
 APPROVAL.
  
 2)NOTE: PLEASE CALRIFY CIRCUTIING FOR
 EM/ EXIT LTS PER 700-12
  
 3)NOTE: PLEASE NOTE RECEPTS REQ`D FOR
 SHOW WINDOWS. PER 210-62
 EXISTING?
  
 PLEASE SEE ANY FIRE REVIEW COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  