| Plan Review Notes For Permit 02091401 |
| Permit Number |
02091401 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-26 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE PLANS NEED TO BE | | | STAMPED BY CITY PLACE FOR CONSTRUCTION | | | APPROVAL. | | | | | | 2)NOTE: PLEASE CALRIFY CIRCUTIING FOR | | | EM/ EXIT LTS PER 700-12 | | | | | | 3)NOTE: PLEASE NOTE RECEPTS REQ`D FOR | | | SHOW WINDOWS. PER 210-62 | | | EXISTING? | | | | | | PLEASE SEE ANY FIRE REVIEW COMMENTS THAT | | | MAY AFFECT ELECTRICAL PLANS. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|