| Notes |
| Date |
Text |
| 2002-09-25 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PAGE #2 OF THE SUBMITTALS INDICATE | | | THE BALLAST FOR THE LIGHTS HAS A 277 | | | VOLT PRIMARY,THE RISER DIAGRAM OF THE | | | PALM STREET LOCATION SHOWS THE PANELS | | | BEING 120/240 VOLT.THE PANELS AT THE | | | OTHER TWO LOCATIONS DON'T HAVE A | | | VOLTAGE RATING. | | | | | | 2} THE PANEL AT THE PALM STREET LOCATION | | | MUST HAVE A MAIN BREAKER PER 381-14(A). | | | | | | 3} THE PLANS INDICATE THAT THE FEEDS | | | FROM FPL TO THE PANELS IS 120 VOLT. | | | | | | PLEASE REVISE PLANS TO CORRECT THESE | | | ERRORS AND SUBMIT SAME FOR REVIEW,BEFORE | | | FINAL INSPECTION. | | | | | | | | | BILL TROBAUGH | | | CITY OF WEST PALM BEACH | | | ELECTRICAL PLAN REVIEW. | | | 561/659-8096 EXT.8392 |
|