Plan Review Notes
Plan Review Notes For Permit 02091330
Permit Number 02091330
Review Stop R
Sequence Number 1
Notes
Date Text
2002-10-17 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-TAKE DRAWINGS TO PALM BEACH COUNTY
 AFTER THEY ARE REVISED TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK PAID
 RECEIPT AND STAMPED DRAWINGS.
 3-PROVIDE ALL THE INFORMATION REQ'D ON
 DRAWINGS. SEE SEC. 1606.1.7 FBC 2001.
 4-ENGINEER TO PROVIDE HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FL. STATUTES
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 5-IDENTIFY ROOMS IN EXISTING HOUSE TO
 VERIFY FOR EGRESS REQUIREMENTS. SEC.
 1005.4.4 FBC 2001. SPECIFY EGRESS FOR
 BEDRMS THAT AFFECTED BY THE ADDITION.
 6-PROVIDE ROOF FRAMING PLAN AND PROVIDE
 DETAILS AND SPECS FOR ATTACHMENT OF
 NEW ROOF TO EXISTING ONE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **CLEARLY SPECIFY SIZE OF TRUSS ANCHOR.
 7-SPECIFY TYPE AND GRADE OF STRUCTURAL
 WOOD USED FOR ROOF FRAMING. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-COMPLETELY SPECIFY HOW'S NEW STRUCTURE
 ATTACHED TO EXISTING ONE. SPECIFY SIZE
 & ATTACHMENT OF DOWELS TO WALLS AND
 FOOTING. SEC. 104.2.1.2 CITY AMENDMENT
 9-CLARIFY IF NEW ROOF IS TO BE FLAT OR
 PITCHED. ELEVATIONS SHOW PITCHED ROOF
 BUT WALL SECTION SHOW FLAT ROOF. ALSO,
 IF FLAT ROOF, THEN REVISE PITH TO 1/4"
 PER FT. SEC. 1508 FBC 2001.
 **NOTE: IF GABLE END, THEN PROVIDE COM-
 PLETE SECTION/DETAIL THAT COMPLIES W/
 SEC. 2117 FBC 2001.
 10-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE SEC. 2405.2 FBC 2001.
 11-PROVIDE ENERGY CALCULATIONS FOR THE
 ADDITION. SEC. 600.2.A.3 CHAPTER 13
 FBC 2001.
 12-SPECIFY FASTENING TYPE & SPACING FOR
 ROOF SHEATHING. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001.
 13-CLARIFY SIZE OF ROOF FRAMING MEMBERS.
 2X10'S OR 2X12'S. SEE HAND WRITTEN
 INFORMATION ON WALL SECTION.
 14-SPECIFY BOND BEAM HEIGHT, REINFORCE-
 MENT. CLARIFY WHAT'S SIMPSON TPGA210
 HURRICANE STRAP (UNABLE TO FIND IN THE
 SIMPSON CATALOGUE) AND WHAT IS IT FOR
 AT THE BOND BEAM?. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 15-SPECIFY WINDOW SILL. SIZE AND REINFOR
 CEMENT. SEC. 104.2.1.2 CITY AMENDMENTS
 16-STORM SHUTTERS: SPECIFY ON PRODUCT
 APPROVAL SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING.
 PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 17-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF SYSTEM (FLAT OR PITCHED)
 B)SINGLE HUNG WINDOWS PRODUCT APPROVAL
 BY PAN AMERICAN: 1)PAN AMERICAN IS OUT
 OF BUSINESS. 2)DRAWINGS AREN'T LEGIBLE
 3)MISSING SOME DRAWINGS.
 C)"STA-TRU" OUTSWING DOOR PRODUCT APPRO-
 VAL: 1)DRAWINGS DON'T MATCH REPORT.
 PROVIDE 2 SETS.
 18-REVISE DOOR STRUCTURAL BUCK DETAIL.
 SEE SEC. 1707.4.4.2 FBC 2001.
 19-SPECIFY WWM SUPPORTS AND SPACING IN
 CONCRETE SLAB. OR DESIGN JOINTS. SEE
 SEC. 1909.3 FBC 2001.
 20-SEE PLANS FOR ADDITIONAL COMMENTS AND
 RETURN REVIEWED SETS AFTER CORRECTIONS
 ARE DONE TO ORIGINAL DRAWINGS TO
 EXPEDITE REVIEW PROCESS.
 21-VALUE DECLARED FOR CONSTRUCTION IS
 TOO LOW. OWES $257.31 FOR VALUATION
 AND RADON FEES.