| 2002-10-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHT A-2.1 HANDICAP STALL MEN'S REST |
| | ROOM, WATER CLOSET CAN NOT INTRUDE INTO |
| | THE CLEAR FLOOR SPACE FOR HDCP LAV. |
| | 2) SHT A10.1 DETAIL #2, FLUSH CONTROLS |
| | TO BE ON CLEAR SIDE OF W/C SEC 11-4.16.5 |
| | 3) SHT A10.1 DETAIL #4, TOILET ROOM TO |
| | BE ADAPTABLE. 11-4.1.3(11). PLEASE SHOW |
| | DETAILS. W/C TO BE 18" OFF WALL, SHOW |
| | BACKING FOR GRAB BARS, LAV TO BE ABLE TO |
| | BE SET AT 34" ECT. |
| | 4) SHT A10.1 DETAIL #3, 1 URNAL TO BE |
| | HDCP PER 11-4.22.5. SHOW HEIGHT SECTION |
| | 11-4.18.2, AND CLEAR FLOOR SPACE SECTION |
| | 11-4.18.3. |
| | 5) SHT P.1 SINK IN SACRISTY SHALL DRAIN |
| | TO SANITARY. SECTION 301.3 |
| | 6) SHTS P.2/P.3 RELIEF VALVE DRAIN SHALL |
| | NOT BE TRAPPED. SECTION 504.7.1 |
| | 7) SHT P.3 WATER RISER DIAGRAM, WATER |
| | HEATER SHALL REQUIRE THERMAL EXPANSION |
| | CONTROL. SECTION 607.3.2 |
| | SHT P-3 WATER RISER DIAGRAM, WATER HAMM- |
| | ER ARRESTORS REQUIRED BY SECTION 604.9 |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE", NOT AT THE TOP OF THE |
| | DROP IN CEILING AS SHOWN PER PDI-WH 201 |
| | AND MANUFACTURE INSTALLATION INSTRUCTION |
| | 8) SEPARATE IRRIGATION PERMIT AND PLANS |
| | ARE REQUIRED. PLUMBING CONTRACTOR SHALL |
| | PROVIDE A VALVE AND ADAPTOR FOR IRRG. |
| | CONTRACTOR. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |