| Plan Review Notes For Permit 02091306 |
| Permit Number |
02091306 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-10 00:00:00 | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRES NOTIFICATION TO ALARM STROBE | | | IN NORMALLY OCCUPIED AREAS OR A SUPER- | | | VISORY SIGNAL TO BE INDICATED AT A | | | CONSTANTLY ATTENDED LOCATION OR CAUSES | | | AN ALARM SIGNAL. NFPA 90A 4-4.4.3 & | | | 4-4.4.2. | | | | | | 2001 FBC(M) 306.5, WHERE EQUIPMENT AND | | | APPLIANCES REQUIRING ACCESS ARE | | | INSTALLED ON ROOFS OR ELEVATED | | | STRUCTURES AT A HEIGHT EXCEEDING 16 FT, | | | SUCH ACCESS SHALL BE PROVIDED BY A | | | PERMANENT APPROVED MEANS OF ACCESS. | | | SUCH ACCESS SHALL NOT REQUIRE CLIMBING | | | OVER OBSTRUCTIONS GREATER THAN 30 | | | INCHES.PLAN SHEET A-3.0 - ROOFPLAN | | | KEYNOTES #8 MAINTENANCE ACCESS HATCH, | | | NO #8 IDENTIFIED ON PLAN. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|