| Plan Review Notes For Permit 02091196 |
| Permit Number |
02091196 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-04 00:00:00 | DENIED:MECHANICAL PERMIT 02091533 | | | | | | AS PER FS/FAC PLANS SHALL HAVE RAISED | | | SEAL AND BE SIGNED/DATED BY THE ENGINEER | | | OR ARCHITECT OF RECORD. | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89.PROVIDE DUCT SIZE, MATERIAL & | | | LAYOUT FOR THE OUTSIDE AIR DUCT. | | | | | | PLEASE NOTE, EXHAUST AIR SHALL NOT BE | | | DIRECTED ONTO WALKWAYS. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|