2002-09-26 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE PLANS ARE COPIES OF
 SIGNED AND SEALED PLANS. PLEASE NOTE
 UNDER FS/FAC ALL PLAN S MUST CONTAIN
 AN ORIG SIGNATURE,RAISED SEAL AND DATED
 BY ARCH/ENGINEER OF RECORD. 471.025,
 481.221.
  
 2)NOTE: IT IS NOTED THAT RISER SHOWS AN
 EXISTING MAIN AND METER. PLEASE CLARIFY
 IF PANEL "A" IS NEW OR EXISTING?
 IF NEW PLEASE PROVIDE AIC RATING OF
 PANEL. 110-9
  
 3)NOTE: PLEASE CLARIFY CIRCUITING FOR
 EM/EXIT LTS PER 700-12
  
 4)NOTE: PLEASE CLARIFY IF NEW OR EXIST-
 -ING SIGN CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PALMER
 561-659-8096 EXT 8372