| Plan Review Notes For Permit 02091172 |
| Permit Number |
02091172 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT CS-1 PLUMBING NOTE #8, 2" AND | | | SMALLER PIPE SHALL PITCH AT 1/4" PER FT. | | | 2) SHTS CS-1 & P-1 PLUMBING NOTES #12. | | | AIR CHAMBERS ARE NOT APPROVED. PLEASE | | | DELETE THEM FROM REFERENCE. | | | 3) SHT P-1 WATER RISER DIAGRAM, WHERE | | | REQUIRED BY SEC 604.9, WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE FIX- | | | TURE IN AN "EFFECTIVE RANGE", NOT AT THE | | | TOP OF THE DROP IN CEILING AS SHOWN. | | | 4) SHT P-1 WATER HEATER DETAIL. IF THERE | | | IS A RPZ BACKFLOW ON THE WATER SERVICE, | | | THAN THERMAL EXPANSION CONTROL PER SEC | | | 607.3.2 WILL BE REQUIRED. SHOW ON DETAIL | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|