Plan Review Notes
Plan Review Notes For Permit 02091172
Permit Number 02091172
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-24 00:00:00************UNSAT *****************
  
 1)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL "A", ALSO PANEL "A" AND PANEL
 "B". SIZE PER 250-122
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220-3,220-10,220-11,220-13 ETX
 PLEASE NOTE CONTINUOUS LOADS AT 125%.
 215-3,230-42
  
 3)NOTE: PLEASE NOTE LOADS SHOWN FOR
 A/C UNITS DO NOT CORRELATE W/ MECH PLANS
 PLEASE NOTE OCP FOR A/C UNITS TO BE
 SIZED PER 424-3.
 PLEASE SHOW LOCATIONS OF UNITS /AND
 DISCONNECTS ON PLANS 440-11.
 RECEPTS PER 210-63.
  
 4)NOTE: PLEASE CLARIFY SHOW ROOM RECEPTS
 REQ`D PER 210-62.
  
 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER
 600-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372