| Notes |
| Date |
Text |
| 2002-09-24 00:00:00 | ************UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND PANEL "A", ALSO PANEL "A" AND PANEL | | | "B". SIZE PER 250-122 | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 220-3,220-10,220-11,220-13 ETX | | | PLEASE NOTE CONTINUOUS LOADS AT 125%. | | | 215-3,230-42 | | | | | | 3)NOTE: PLEASE NOTE LOADS SHOWN FOR | | | A/C UNITS DO NOT CORRELATE W/ MECH PLANS | | | PLEASE NOTE OCP FOR A/C UNITS TO BE | | | SIZED PER 424-3. | | | PLEASE SHOW LOCATIONS OF UNITS /AND | | | DISCONNECTS ON PLANS 440-11. | | | RECEPTS PER 210-63. | | | | | | 4)NOTE: PLEASE CLARIFY SHOW ROOM RECEPTS | | | REQ`D PER 210-62. | | | | | | 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER | | | 600-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|