| 2002-10-17 00:00:00 | SHEET SP1 SHOWS THE DOORS SWINGING OVER |
| | THE RIGHT OF WAY.THIS IS PROHIBITTED |
| | BY FBC 3203, PLEASE REVISE AS NECESSARY. |
| | |
| | SHOW THE MIXED OCCUANCY SEPARATION |
| | BETWEEN THE WAREHOUSE "S" AND THE |
| | SHOWROOM / OFFICES "B" AS REQUIRED BY |
| | FBC 704.1.1 (2 HR) |
| | |
| | THE STAIRS FROM THE SECOND FLOOR ARE |
| | REQUIRED TO BE ENCLOSED IN A FIRE RATED |
| | SHAFT.SEE FBC 1006.1.1.THE SECOND |
| | FLOOR IS NOT A MEZZANINE AS DEFINED IN |
| | FBC 503.2.3. |
| | |
| | SHEET S1 SECTION 1.SPECIFY THE |
| | SIMPSONHB ANCHOR AND WELD TO BE USED. |
| | |
| | S1, IS THE 2X12 SPLICE SHOWN WITH 12 |
| | NAILS OCCUR AT MID SPAN?WHAT IS THE |
| | ANTICIPATED LOAD VALUE? |
| | |
| | S1, WHAT IS THE 5/8" PLYWOOD DECK ON THE |
| | SECOND FLOOR TO BE USED FLOOR? IS IT |
| | ENCLOSED? |
| | |
| | THE 42" FOOTINGS SHOWN ON S1 CONFLICT |
| | WITH THE 36" SQUARE FOOTINGS ON A4. |
| | PLEASE CLARIFY. |
| | |
| | SHEET A1 PLAN "A", THE ELEVATOR DOOR |
| | AND THE SHOW WINDOW DOOR 4, SHOWN DO |
| | NOT COMPLY WITH FBC 1012.1.4. |
| | |
| | IF THE TEST REPORTS FOR THE DOORS, |
| | WINDOWS AND ROOF COVERINGS ARE NOT |
| | INCLUDED WITH THIS PERMIT APPLICATION, |
| | A SEPARATE PERMIT AND FEES WILL BE |
| | REQUIRED. |
| | |
| | THE GLASS BLOCK MUST BE INSTALLED IN |
| | ACCORDANCE WITH FBC 2112. |