Plan Review Notes For Permit 02091172
Permit Number 02091172
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-17 00:00:00SHEET SP1 SHOWS THE DOORS SWINGING OVER
 THE RIGHT OF WAY.THIS IS PROHIBITTED
 BY FBC 3203, PLEASE REVISE AS NECESSARY.
  
 SHOW THE MIXED OCCUANCY SEPARATION
 BETWEEN THE WAREHOUSE "S" AND THE
 SHOWROOM / OFFICES "B" AS REQUIRED BY
 FBC 704.1.1 (2 HR)
  
 THE STAIRS FROM THE SECOND FLOOR ARE
 REQUIRED TO BE ENCLOSED IN A FIRE RATED
 SHAFT.SEE FBC 1006.1.1.THE SECOND
 FLOOR IS NOT A MEZZANINE AS DEFINED IN
 FBC 503.2.3.
  
 SHEET S1 SECTION 1.SPECIFY THE
 SIMPSONHB ANCHOR AND WELD TO BE USED.
  
 S1, IS THE 2X12 SPLICE SHOWN WITH 12
 NAILS OCCUR AT MID SPAN?WHAT IS THE
 ANTICIPATED LOAD VALUE?
  
 S1, WHAT IS THE 5/8" PLYWOOD DECK ON THE
 SECOND FLOOR TO BE USED FLOOR? IS IT
 ENCLOSED?
  
 THE 42" FOOTINGS SHOWN ON S1 CONFLICT
 WITH THE 36" SQUARE FOOTINGS ON A4.
 PLEASE CLARIFY.
  
 SHEET A1 PLAN "A", THE ELEVATOR DOOR
 AND THE SHOW WINDOW DOOR 4, SHOWN DO
 NOT COMPLY WITH FBC 1012.1.4.
  
 IF THE TEST REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERINGS ARE NOT
 INCLUDED WITH THIS PERMIT APPLICATION,
 A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED.
  
 THE GLASS BLOCK MUST BE INSTALLED IN
 ACCORDANCE WITH FBC 2112.