2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING.
  
 1) PLEASE SUBMIT A SANITARY AND A WATER
 RISER DIAGRAM. SHOW ALL PIPE SIZES,
 WATER HAMMER ARRESTORS (REQD. 604.9) ECT
 2) ONLY THE FIXTURES OF A BATHROOM GROUP
 CAN DRAIN INTO THE WET VENTED SYSTEM OF
 A BATHROOM. WASH MACHINE AND HAIR SINK
 WILL HAVE TO DRAIN DOWNSTREAM OF THE
 BATHROOM GROUP. SEC 909.1/909.2
  