| 2002-11-04 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE A COMPLETE SOIL TEST REPORT |
| | INDICATING SOIL BEARING CAPACITY. REPORT |
| | IS REQUIRED TO BE SIGNED, SEALED AND |
| | DATED BY A FLORIDA SOIL ENGINEER. |
| | |
| | 4) THE INTERNAL PRESSURE COEFFICIENT ON |
| | A1 SHOULD BE DESIGNATED + AND - TO |
| | INDICATE THE INWARD AND OUTWARD FORCES. |
| | |
| | 5) PROVIDE SPECIFICATIONS FOR THE 4X8 |
| | SOLID PRE-CAST LINTEL BETWEEN ENTRY DOOR |
| | AND FIXED GLASS TRANSOM. PROVIDE A |
| | LINTEL SCHEDULE FOR ALL LINTELS. |
| | |
| | 6) CLARIFY GLASS BLOCK NOTE ON A8. GLASS |
| | BLOCK IN WALLS ENCLOSING TUBS, SHOWERS, |
| | ETC. AND WITHIN 36" HORIZONTALLY OF A |
| | STANDING OR WALKING SURFACE IS REQUIRED |
| | TO HAVE A UNIFORM FACE THICKNESS OF |
| | 0.25 INCH PER FBC 2405.2.2. |
| | |
| | 7) THE THICKNESS OF THE STEEL HEADER IS |
| | GIVEN AS 1-1/4" ON A8. PLEASE CLARIFY. |
| | |
| | 8) PROVIDE (2) COPIES OF A KEY PLAN AND |
| | A CORRESPONDING INSTALLATION SCHEDULE |
| | INDICATING THE SPECIFIC TYPE OF ANCHORS |
| | USED FOR THE HURRICANE PANELS. INDICATE |
| | THE MOUNTING OPTIONS THAT WILL BE USED. |
| | NOTE: THIS INFORMATION IS REQUIRED AT |
| | THIS TIME OR YOU WILL BE REQUIRED TO |
| | PULL A SEPARATE PERMIT AND PAY |
| | ADDITIONAL FEES. |
| | |
| | 9) THE SLIDING GLASS DOOR PRODUCT |
| | APPROVALS ARE MISSING THE SECOND PAGE. |
| | THE PRODUCT ACCEPTANCE NUMBERS ON THE |
| | DRAWINGS ARE DIFFERENT FROM THOSE ON THE |
| | PRODUCT APPROVAL. |
| | |
| | 10) PROVIDE SPECIFICATIONS FOR THE ONE |
| | HOUR FIRE RATED ASSEMBLY AND THE UL |
| | LISTING INFORMATION. |
| | |
| | 11) PLEASE REMOVE THE PRODUCT APPROVALS |
| | FOR THE GLASS BLOCK THAT YOU WILL NOT BE |
| | USING. SUBMIT THE PRODUCT APPROVALS FOR |
| | ONLY THE PRODUCT THAT ARE GOING TO BE |
| | INSTALLED. |
| | |
| | 12) IN ORDER TO MEET THE WINDLOAD |
| | PRESSURES LISTED ON THE PLANS, THE FIXED |
| | GLASS ARCHED AND TRANSOM WINDOWS NEED TO |
| | BE 3/16" TEMPERED GLASS. TEMPERED GLASS |
| | IS NOT INDICATED ON THE PLANS FOR THESE |
| | WINDOWS. |
| | |
| | 13) INDICATE ON THE SINGLE HUNG WINDOW |
| | PRODUCT APPROVALS THE TYPE OF GLASS TO |
| | BE USED. NOTE: SOME OF THE GLASS TYPES |
| | WILL NOT MEET THE DESIGN PRESSURES |
| | REQUIRED BY THE PLANS. |
| | |
| | 14) THE SITE SPECIFIC PRODUCT APPROVAL |
| | FORMS FOR THE EXTERIOR SIDE SWING DOORS |
| | ARE REQUIRED TO BE SIGNED, SEALED AND |
| | DATED BY THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. THE LOCATION OF THE STRUCTURE |
| | IS REQUIRED TO BE ON THE FORMS. THE TEST |
| | REPORTS ARE REQUIRED WHEN IMPACT |
| | RESISTANCE IS INDICATED. SEE ITEM 7.5 |
| | ON THE FORM. |
| | |
| | 15) PROVIDE PRODUCT APPROVALS FOR |
| | VERTICAL STRUCTURAL MULLIONS AT WINDOWS. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |