| Plan Review Notes For Permit 02091077 |
| Permit Number |
02091077 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-02 00:00:00 | ************ NOTES/REVISIONS ****** | | | | | | 1)NOTE: PLEASE NOTE,NO MAIN IN PANEL/ | | | REQ`D PER 225-31. | | | | | | 2)NOTE: PLEASE NOTE RECEPTS TO BE WITHIN | | | 3' OF SINK. 210-52D | | | | | | 3)NOTE: PLEASE NOTE IF DEN/LIBARY IS | | | CONVERTED TO SLEEPING ROOM. A SD IS | | | REQ`D INSIDE AND OUTSIDE. | | | NFPA-72 2-2.1.1.1 | | | | | | 4)NOTE: PLEASE NOTE MISSING RECEPTS PER | | | 210-52. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|