Plan Review Notes
Plan Review Notes For Permit 02091075
Permit Number 02091075
Review Stop R
Sequence Number 1
Notes
Date Text
2002-10-15 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAID IMPACT FEES. BRING STAMPED DWGS
 AND PAID RECEIPT.
 3-PROVIDE COMPLETE SOIL TEST REPORT WITH
 ORIGINAL SIGNATURE AND ENGINEER'S SEAL
 AS REQUIRED BY CHAPTER 471 FL STATUTE.
 **NOTE: PRELIMINARY BORING SHOW ORGANIC
 SOIL. REMOVE AS REQ'D BY SEC. 1804.1.8
 FBC 2001.
 **SOIL TEST REPORT TO SPECIFY SOIL PREP.
 AND SOIL BEARING CAPACITY.
 4-DRAWINGS TO INCLUDE ALL INFORMATION
 REQUIRED BY SEC. 1606.1.7 FBC 2001.
 5-SHEET A-3: A)CLARIFY COLS. SPECIFIED
 FOR GARAGE DOOR. DRAWING SHOWS FILLED
 CELLS BUT NOTE CALLS FOR POURED CONC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 B)SPECIFY SUPPORTS AND SPACING FOR WWM
 ON CONCRETE SLAB. SEC. 1909.3 FBC 2001
 6-SHEET A-5: A)SPECIFY ONE HOUR FIRE
 RATED GLASS BLOCK ASSEMBLY AT ZERO LOT
 LINE. TABLE 600 FBC 2001.
 B)PROVIDE STRUCTURAL DETAIL FOR BOLLARD
 OR 3" STEEL POST AT GARAGE. SEC .
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)PROVIDE COMPLETE STRUCTURAL DETAILS
 AND SPECS FOR 4X8 SOLID LINTEL FOR
 DOORS AND WINDOWS ASEMBLIES W/ TRANSOM
 ABOVE. SEC. 104.2.1.2 CITY AMENDMENTS.
 D)GARAGE VENTILATION IS NOT ALLOWED AT
 ZERO LOT LINE WALL. TABLE 600 FBC 2001
 NOT OPENINGS ALLOWED.
 E)PROVIDE ATTIC ACCESS ABOVE GARAGE.
 SEC. 2309.6 FBC 2001.
 F)CONSTRUCTION TYPE SPECIFIED IS WRONG.
 REVISE AS REQUIRED. SEE CHAPTER 6 FBC.
 7-SHEET A-6: A)PROVIDE ATTIC ACCESS.
 SEC. 2309.6 FBC 2001.
 B)SPECIFY SAFETY GLASS FOR WINDOWS AT
 MASTER BATH & BATH 2. SEC. 2405.2 FBC
 **NOTE: GLASS BLOCK IN MASTER BATH TO BE
 SAFETY GLASS IF UNIFORM FACE THICKNESS
 IS LESS THAN 0.25". SEC. 2405.2.2 FBC.
 C)SPECIFY ONE HR FIRE RATED GLASS BLOCK
 AT ZERO LOT LINE WALL. TABLE 600 FBC.
 D)WRITE ON PLAN THAT LOFT AREA IS NOT TO
 BE USED FOR SLEEPING PURPOSES OR PROVI
 DE WINDOW THAT COMPLIES WITH EGRESS
 REQUIREMENTS. SEC. 1005.4.4 FBC 2001.
 8-SHEET A-7: A)PROVIDE COMPLETE SECTION
 DETAIL AT REAR PORCH SHOWING RAILING
 INSTALLATION TO COMPLY WITH SECTION
 1608.2 FBC 2001.
 B)SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION ON 2ND FLOOR FRAMING PLAN.
 SEC. 2305.2.2 FBC 2001. DO NOT CITE
 AS PER CODE. BE SPECIFIC.
 C)SPECIFY FIREBLOCKING MATERIAL & LOCA-
 TION AT STAIR SECTION. SEE SECTION
 2305.1.4 FBC FOR REQUIRED LOCATION.
 **NOTE: PROVIDE GENERAL SPECIFICATIONS
 FOR FIREBLOCKING REQUIRED AT ALL
 CONCEALED SPACES. SEE SEC. 2305.1.4
 D)REVISE TITLE OF DRAWING. THIS IS THE
 2ND FLOOR FRAMING PLAN NOT 1ST FLOOR.
 9-SHEET A-8: A)SPECIFY CONNECTORS FOR
 ALL BEAMS @ FRONT PORCH. SEC 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)REVISE UPLIFT VALUE FOR DOUBLE TA13
 CONNECTOR. SEE LATEST USP CATALOGUE
 FOR ENGINEERED VALUE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 10-SHEET A-12: A)REVISE NAILING SCHEDULE
 FOR ROOF SHEATHING. NEED 8D RING SHANK
 FOR ROOF ABOVE 25" MEAN ROOF HEIGHT.
 SEE TABLE 2306.1 CITY AMENDMENTS FBC.
 11-SHEET A-13: A)REVISE GENERAL NOTES.
 HUGHES AND SEMCO CONNECTORS ARE OUT
 OF BUSINESS.
 B)REVISE GLASS BLOCK DETAIL. SEE UL
 SPECS FOR ONE HR FIRE RATED ASSEMBLY.
 REQUIRED BY TABLE 600 FBC 2001.
 C)PROVIDE COMPLETE INFORMATION FOR 2"
 STEEL HEADER DETAIL. NEED TO SPECIFY
 WELDING FOR PLATE & COMPLETE SPECS FOR
 STEEL TUBE TO BE USED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D)SPECIFY SIZE OF WASHER GARAGE DOOR
 BUCK DETAIL. SEC. 104.2.1.2 CITY AMEND
 E)SCREEN ENCLOSURE UNDER SEPARATE PERMIT
 F)REVISE DETAIL FOR SWING DOOR JAMB. SEE
 SEC. 1707.4.4.2 FBC 2001.
 12-STORM SHUTTERS:A)PROVIDE COMPLETE KEY
 PLAN AND INSTALLATION SCHEDULE (SEE
 CITY SAMPLE).
 B)PROVIDE DADE COUNTY OR SBCCI PRODUCT
 APPROVAL OR SEE ITEMS 15, 16 AND 17 OF
 CITY IMPLEMENTATION STANDARD FOR HU-
 RRICANE MISSILE IMPACT PROTECTION FOR
 SITE SPECIFIC PRODUCT APPROVALS.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)EXTERIOR SWING DOORS @ ENTRY & 2ND FL.
 BROWARD COUNTY PRODUCT APPROVAL IS NOT
 ACCEPTED. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR SITE SPECIFIC
 INSTALLATIONS. ***NOTE: SEE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 B)CLARIFY WHICH GLASS BLOCK MANUFACTURER
 IS GOING TO BE USED. PROVIDE COMPLETE
 UL SPECS FOR 1HR FIRE RATED ASSEMBLY.
 **NOTE: SAFETY GLASS REQUIRED IF FACE
 THICKNESS IS LESS THAN 0.25".
 C)FIXED WINDS PRODUCT APPROVAL: CLEARLY
 INDICATE WHICH TYPE OF WINDOWS TO BE
 USED (IMPACT, NON IMPACT).
 **SOME WINDOWS DON'T MEET THE DESIGN PRE
 SSURES CALCULATED BY THE ARCHITECT.
 **PRODUCT APPROVAL TO SPECIFY ANCHORING
 TO THE STEEL TRANSOM AS SHOWN ON PLANS
 D)SLIDING GLASS DOORS DRAWINGS DON'T
 MATCH PRODUCT APPROVAL. SEE ACCEPTANCE
 NUMBER BY DADE COUNTY.
 **MISSING PAGE TWO OF PRODUCT APPROVAL.
 **SEE DESIGN PRESSURES CALCULATED BY
 ARCHITECT.
 E)PROVIDE PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOWS THAT MEET THE DESIGN PRE-
 SSURES CALCULATED BY ARCHITECT. EG:
 SEE WINDOWS J, O, LL AND MM.
 F)PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS.
 14-OWES $152.92 FOR UPDTED VALUATION AND
 RADON FEES.
  
 NOTE: PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS AE DONE TO ORIGINAL DWGS TO
 EXPEDITE REVIEW PROCESS.