Plan Review Notes
Plan Review Notes For Permit 02091027
Permit Number 02091027
Review Stop B
Sequence Number 4
Notes
Date Text
2004-06-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02091027
 ADD: 1600 PRESIDENTIAL WAY
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL: FIRE RATED CHASE FOR ELECTRIC
 AL CONDUIT IN STAIR TOWER
  
 ACTION: DENIED
 1) 1006.1.3.1 PENETRATIONS INTO & OPEN-
 INGS THROUGH A STAIRWAY ENCLOSURE
 ASSEMBLY ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, DUCTWORK & EQUIP-
 MENT NECCESSARY FOR INDEPENDENT STAIR
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, AND ELECTRICAL CONDUIT SERV-
 ING THE STAIRWAY AND TERMINATING AT A
 STEEL BOX NOT EXCEEDING 16 SQ IN.SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH 705.4. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS,
 WETHER PROTECTED OR NOT, BETWEEN ADJA-
 CENT STAIRWAYS.
  
 2) THE SECOND ISSUE IS NO LOCATION IS
 GIVEN IN THE STAIRWAY, SEE 1007.4.2.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026