4 |
|
| Notes |
| Date |
Text |
| 2004-06-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 02091027 | | | ADD: 1600 PRESIDENTIAL WAY | | | CONT: AVS CONSTRUCTION | | | TEL: (954)655-5162 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | SUBMITTAL: FIRE RATED CHASE FOR ELECTRIC | | | AL CONDUIT IN STAIR TOWER | | | | | | ACTION: DENIED | | | 1) 1006.1.3.1 PENETRATIONS INTO & OPEN- | | | INGS THROUGH A STAIRWAY ENCLOSURE | | | ASSEMBLY ARE PROHIBITED EXCEPT FOR | | | REQUIRED EXIT DOORS, DUCTWORK & EQUIP- | | | MENT NECCESSARY FOR INDEPENDENT STAIR | | | PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, AND ELECTRICAL CONDUIT SERV- | | | ING THE STAIRWAY AND TERMINATING AT A | | | STEEL BOX NOT EXCEEDING 16 SQ IN.SUCH | | | PENETRATIONS SHALL BE PROTECTED IN | | | ACCORDANCE WITH 705.4. THERE SHALL BE NO | | | PENETRATIONS OR COMMUNICATING OPENINGS, | | | WETHER PROTECTED OR NOT, BETWEEN ADJA- | | | CENT STAIRWAYS. | | | | | | 2) THE SECOND ISSUE IS NO LOCATION IS | | | GIVEN IN THE STAIRWAY, SEE 1007.4.2. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|