2002-11-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT P-1 LETTER FROM RODNEY COMPO RE-
 QUIRES A SAMPLE POINT. PLEASE INDICATE
 ON RISER DIAGRAM AND FLAT DRAWING.
 (SEE SHT P-1 FOR LOCATION)
 2) SHT P-1 WASH MACHINE SHALL NOT DRAIN
 INTO GREASE WASTE LINE, (SEE SHT P-1 FOR
 CHANGE REQUIRED.)
 3) RPZ BACKFLOW REQUIRED. PLEASE INDICA-
 TE ON PLANS. BACKFLOW SHALL BE LOCATED
 MAXIMUM OF 4' A.F.F. AND DRAINED IN-
 DIRECTLY INTO A FLOOR SINK OR THE MOP
 SINK.
  