Plan Review Notes
Plan Review Notes For Permit 02091026
Permit Number 02091026
Review Stop P
Sequence Number 1
Notes
Date Text
2002-10-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) GREASE TRAP SIZING SHALL BE BY ROD
 COMPO (561) 837-4074. WASTE ORD. #2938-
 96. IF EXISTING GREASE LINE IN SPACE,
 TIE FLOOR DRAINS, THREE COMP. SINK AND
 MOP SINK INTO GREASE LINE.
 2) SHT P-1, FLOOR DRAIN IN WOMENS TOILET
 ROOM #103 IS NOT VENTED. PLEASE DRAIN
 FLOOR DRAIN INTO VENTED LINE FOR LAV.
 3) SHT P-1 GENERAL NOTES #16. AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE.
 4) SHT P-1, FLOOR DRAIN FOR FREEZER COND
 ENSATE NOT APPROVED. FLOOR SINK REQUIRED
 FOR ALL INDIRECT WASTE. SEC 802.3
 5) SHT P-1, WATER RISER DIAGRAM, PLEASE
 MOVE WATER HAMMER ARRESTORS NEXT TO
 WASHER (BETWEEN LAST TWO FIXTURES) AS
 THEY ARE REQUIRED AT WASH MACHINES.
 6) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377