| Notes |
| Date |
Text |
| 2002-10-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) GREASE TRAP SIZING SHALL BE BY ROD | | | COMPO (561) 837-4074. WASTE ORD. #2938- | | | 96. IF EXISTING GREASE LINE IN SPACE, | | | TIE FLOOR DRAINS, THREE COMP. SINK AND | | | MOP SINK INTO GREASE LINE. | | | 2) SHT P-1, FLOOR DRAIN IN WOMENS TOILET | | | ROOM #103 IS NOT VENTED. PLEASE DRAIN | | | FLOOR DRAIN INTO VENTED LINE FOR LAV. | | | 3) SHT P-1 GENERAL NOTES #16. AIR CHAMB- | | | ERS ARE NOT APPROVED. PLEASE DELETE REF- | | | ERENCE. | | | 4) SHT P-1, FLOOR DRAIN FOR FREEZER COND | | | ENSATE NOT APPROVED. FLOOR SINK REQUIRED | | | FOR ALL INDIRECT WASTE. SEC 802.3 | | | 5) SHT P-1, WATER RISER DIAGRAM, PLEASE | | | MOVE WATER HAMMER ARRESTORS NEXT TO | | | WASHER (BETWEEN LAST TWO FIXTURES) AS | | | THEY ARE REQUIRED AT WASH MACHINES. | | | 6) RPZ BACKFLOW REQUIRED ON WATER SERV- | | | ICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|